Burnham SCG User Manual
Page 10
 
10
A.
Vent Guidelines Due to Removal of an Existing 
Boiler 
For installations not involving the replacement of an 
existing boiler, proceed to Step B.
When an existing boiler is removed from a common 
venting system, the common venting system is likely 
to be too large for proper venting of the remaining 
appliances. At the time of removal of an existing 
boiler, the following steps shall be followed with each 
appliance remaining connected to the common venting 
system placed in operation, while the other appliances 
remaining connected to the common venting system are 
not in operation:
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no 
blockage or restriction, leakage, corrosion, and other 
defi ciencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which 
the appliances remaining connected to the common 
venting system are located and other spaces of the 
building. Turn on clothes dryers and any appliance 
not connected to the common venting system. 
Turn on any exhaust fans, such as range-hoods and 
bathroom exhausts, so they will operate at maxi mum 
speed. Do not operate a summer exhaust fan. Close 
fi replace dampers.
4. Place in operation the appliance being inspected.
Follow the Lighting (or Operating) Instructions. 
Adjust thermo stat so appliance will operate 
continuously.
5. Test for spillage at the draft hood relief opening
after fi ve (5) minutes of main burner operation. Use 
the fl ame of a match or candle, or smoke from a 
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remain ing connected to the common venting system 
properly vents when tested as outlined above, return 
doors, win dows, exhaust fans, fi replace dampers and 
any other gas burning appliance to their previous 
conditions of use.
7. Any improper operation of the common venting
system should be corrected so the installation 
conforms with the National Fuel Gas Code, NFPA 
54/ANSI Z223.1. When resizing any portion of the 
common venting system, the common venting 
system should be resized to approach the minimum 
size as determined using the appropriate tables in 
Part II in the National Fuel Gas Code, NFPA 54/
ANSI Z223.1.
B.
General Guidelines
1. Vent system installation must be in accordance
with National Fuel Gas Code, NFPA 54/ANSI 
Z221.3 or applicable provisions of local building 
codes. Contact local building or fi re offi cials about 
restrictions and installation inspection in your area.
2. The SCG is designed to be installed as either
a Direct Vent boiler or Power Vent boiler. In 
the Direct Vent confi guration all of the air for 
combustion is supplied directly to the burner 
enclosure from outdoors and fl ue gases are vented 
directly outdoors (through wall or roof). In the 
Power Vent confi guration, room air provides air 
for combustion and ventilation. Flue gases are still 
vented directly outdoors (through wall or roof).
Note: Venting requirements change if indoor air is 
used.
3. Refer to the appropriate drawings in this section of
this manual to determine the proper confi guration of 
venting system. See Table 1.
4. This appliance requires a Special Gas Vent. The
product is designed to use Burnham supplied 
AL 29-4C
®
Stainless Steel vent system components.
The following manufacturers offer similar 
AL 29-4C
®
components and are approved for use
with this product. Heat-Fab Inc. - Saf-T-Vent, Flex-L 
International Inc. - Star-34, Z-Flex U. S., Inc. - 
Z-Vent, and Protech Systems , Inc.- FasNSeal™ or 
equivalent. The use of these alternate manufacturer’s 
venting systems will require adapters to connect 
to the Burnham supplied vent connector and vent 
terminal. These adapters are not supplied with this 
unit and should be obtained from the supplier of 
the alternate manufacturer’s venting system. See 
Table 3 for complete list of Burnham Vent System 
Components.
5. Horizontal vent pipe must maintain a minimum ¼
inch per foot slope down towards boiler.
6. Use noncombustible ¾ inch pipe strap to support
horizontal runs and maintain vent location and 
slope while preventing sags in pipe. Do not restrict 
thermal expansion or movement of vent system. 
Maximum support spacing is fi ve (5) feet. Do not 
penetrate any part of the vent system with fasteners. 
7. Vent length restrictions are based on equivalent
length of vent/air pipe (total length of straight 
pipe plus equivalent length of fi ttings). Maximum 
vent/air lengths are listed in Table 4. Do not exceed 
maximum vent/air intake lengths. Table 3 lists 
equivalent lengths for fi ttings. Do not include vent/
air terminals in equivalent feet calculations. 
8. Provide and maintain vent pipe minimum clearances
to combustible materials. Vent pipe minimum 
clearance to combustible material is four (4) inches 
when vent is installed in a fully enclosed (chase) 
application or three (3) inches when vent is installed