a. Wipe the male end of each joint using an alcohol
pad to remove any dirt and grease.
b. Align weld seams in pipes and use a slight
twisting motion to FULLY insert male end into 
female end of joint. Ensure bead in male end 
of pipe is below locking band and rest against 
the end of the female pipe. Verify the factory-
installed gasket is not dislodged or cut.
c. Tighten locking band by HAND with a 5/16”
nut driver until snug plus ¼ turn. DO NOT 
SECURE JOINTS WITH SHEET METAL 
SCREWS OR POP RIVETS. DO NOT 
PUNCTURE THE VENT SYSTEM!
d. Once the installation is complete, operate
appliance and inspect all joints to ensure that fl ue 
gases and/or liquid condensate will not escape. 
D.
Separate Horizontal Venting System.
See Figures 4,
5A and 5B.
Vent Piping
–
1. This boiler is supplied with components as standard
equipment for installation of the separate horizontal 
venting system.
2. Do not exceed maximum vent/air intake lengths.
Refer to Table 4.
3. Recommended horizontal installation consists of
vent being sloped down ¼ inch per foot away from 
boiler. See Figure 4.
4. Use appropriate designed thimbles when passing
through combustible walls (thimble use optional for 
noncombustible walls). Insert thimble through wall 
from outside. Secure outside fl ange to wall with 
nails or screws, and seal ID, OD and vent holes with 
sealant material. Install inside fl ange to inside wall, 
secure with nails or screws, and seal with sealant 
material.
5. For noncombustible wall application when thimble
is not used, size opening such that bell with locking 
band attached cannot pass through.
6. Join vent terminal to vent pipe. See Figures 5A and
5B.
7. Insert vent pipe through thimble/opening from
outside and join to vent system. Apply sealant 
between vent pipe and opening/thimble to provide 
weathertight seal.
Air Intake piping
- See Figures 4, 5A and 5B.
8. Locate air intake termination on the same wall as
the vent termination if possible, to prevent nuisance 
boiler shutdowns. However, boiler may be installed 
with vertical venting and sidewall combustion air 
inlet or visa versa, if installation conditions do not 
allow alternate arrangement.
9. Do not exceed air intake length. See Table 4.
10. Use single wall metal or PVC pipe.
a. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping.
SCG-5 & SCG-6 uses 4 inch diameter piping.
SCG-7 thru SCG-9 uses 5 inch diameter piping.
11. Air intake termination must be located:
Horizontal - At least twelve (12) inches above 
grade plus the expected snow accumulation.
12. Start at collar on burner enclosure (inside boiler
jacket) and work towards the air intake terminal.
13. Maintain minimum of ¼ inch per foot slope on
horizontal runs. Slope towards air inlet terminal 
when possible. If not, slope towards boiler.
14. The air intake pipe must be adequately supported
with straps or supports no less than fi ve (5) feet 
apart on horizontal runs. The complete air intake 
piping system must be rigid and able to withstand 
minor impacts without collapse.
15.
Inlet air pipe penetration
:
Horizontal - Size wall penetration to allow easy 
insertion of air inlet piping. Seal around pipe with 
sealant to form weathertight exterior joint.
16. Seal all joints airtight, using silicone caulk or self-
adhesive aluminum tape.
17.
Install Air Intake Terminal
:
Horizontal - Remove four (4) screws from cover 
plate and remove cover plate from terminal. Insert 
intake piping into intake terminal collar. Secure 
terminal to intake piping and seal joint with silicone 
caulk or self-adhesive aluminum tape. Apply 
continuous bead of silicone caulk around the back 
of the intake terminal, approximately ¼ inch from 
its edge. Push inlet terminal inward until terminal’s 
back fl ange is against the wall surface. Secure the 
terminal with noncorrosive fasteners (stainless steel, 
brass or aluminum) to the wall. Reinstall the cover 
plate with four (4) screws. Apply a bead of silicone 
caulk to perimeter of intake terminal’s back fl ange 
to provide a weathertight seal.