I/P TRANSDUCERS

The “standard” 3-15 psi signal was originally designed as a transmission
signal, not a valve actuation signal. The Fluid Controls Institute (in
Standard 87-2) has recommended that a 1–17 psi air signal range be used
when directly actuating a control valve without a positioner. Powers
concurs with this recommendation, and therefore, offers a 1–17 psi I/P
transducer and a 0–30 psi I/P transducer and the Accritem pneumatic
controller for maximum close-off. 3-15 psi I/P transducers should be used
in conjunction with positioners.

POSITIONERS

Positioners are used for one or more of the following reasons:

1) To split range valves.
2) To eliminate unwanted valve movement caused by line pressure

variations

3) To minimize the effects of “stick-slip”
4) To speed response time
5) To increase close-off rating when I/Ps are used.

Page 8

TI597SI

CODE

PNEUMATIC DIAPHRAGM ACTUATORS

4C

46 Sq. In., 1” Max Valve Stroke Extreme Cycle Springs,
adjustable start w/6-12 lb. fixed span.

1U (for 6" valve only) 100 Sq. In; 8-13 psi Spring Range, (Normally Closed Valves)
1L (for 6" valve only)

100 Sq. In; 3-8 psi Spring Range, (Normally Open Valves)

CODE DESCRIPTION

Bellofram 1000 I/P’S

IS

3–15 psi

TS

1–17 psi

US

3–27 psi

CONTROL/AIR TYPE 900X I/P

ES

0–30 psi

UTILITY POSITIONER AND I/P

BS

4–20 mA

UTILITY POSITIONER

PS

3-15 psi

RS

3-9 psi

SS

9-15 ps

NO ACCESSORIES

OS

No Accessories

ACCESSORIES SELECT CODE

ACTUATOR SELECT CODE

ORDERING INFORMATION

© 2007 Powers

USA: Phone: 1.800.669.5430 • Fax 1. 847. 229 . 0526 • www.powerscontrols.com

Canada: Phone: 1.888.208.8927 • Fax 1. 888. 882 .1979 • www.powerscontrols.ca

TI597SI 0708