Thermostatic water mixing valves are control devices which

must be cleaned and maintained on a regular basis.
1. Before servicing checkstops or piping, turn off the water

upstream. At least every twelve (12) months, open up the

checkstops, and check for the free movement of the poppet.

2. Before servicing the valve, turn off the water supply

upstream or close the checkstops. To close the checkstops,

turn the adjusting screw clockwise.

3. When opening checkstops after servicing, turn adjusting

screw counterclockwise to fully open position. Then turn

adjusting screw 1/2 turn clockwise for final setting.

4. Every three (3) months, check the maximum temperature

adjustments.

5. Every twelve (12) months, remove the valve bonnets and

check the internal components for freedom of movement.

CAUTION:
Any changes in supply condition could effect the out-

let water temperature. Check and adjust the valves

accordingly to prevent injury to the users.

Preventative Maintenance

n

See enclosed IS-P-MM430 and IS-P-SH1430.

Part List For Valve

n

What to look for if:
• Outlet temperature is too hot with low flow:
1. The maximum temperature of the low flow valve was not

properly set. Refer to Set Up Procedure and reset the maxi-

mum temperature of the low flow valve.

2. The thermal actuator of the low flow valve is not working

properly. Replace thermal actuator.

• Outlet temperature is too hot with a high flow:
1. The maximum temperature of a high flow valve was not

properly set. Refer to Set Up Procedure and reset the maxi-

mum temperature of the high flow valve.

2. The thermal actuator of the high flow valve is not working

properly. Replace accordingly, see IS-P-MM430 enclosed.

• Outlet temperature too low with low and high flow:
1. The hot water temperature is too low. You must have a sup-

ply temperature of at least 5º F (3º C) higher than the set

temperature. Readjust the hot water supply.

2. The checkstops on the hot side of the valve are not fully

open, or may be stuck due to liming. Open and clean check

stops.

3. The temperature has not been set properly on the small

and/or large valve. Refer to Set Up Procedure and reset the

valves.

• Outlet flow drops off:
1. The differential across the PRV is set too high, so the

high flow valve begins controlling the system too late,

and starves the system. Refer the Set Up Procedure and

decrease the differential across PRV.

2. The checkstops on the high flow valves are not fully open or

are stuck due to liming. Open and clean checkstops

3. The system pressure varies by more than 50% of the inlet

supply pressure.

• Outlet temperature cycles between hot and cold:
1. The differential across the PRV is set too low, so the high

flow valve begins controlling the system too early, and

therefore cycles (hunt for the set point). Refer to the Set Up

Procedure and increase the differential across PRV.

2. The system pressure varies by more than 50% of the inlet

supply pressure.

Troubleshooting

n

Warranty

n

The Seller warrants that the equipment manufactured by it and covered by this order or contract is free from defects in material and workmanship and, without

charge, equipment found to be defective in material or workmanship will be repaired, or at Seller’s option replaced F.O.B. original point of shipment, if written

notice of failure is received by Seller within one (1) year after date of shipment (unless specifically noted elsewhere), provided said equipment has been properly

installed, operated in accordance with the Seller’s instructions, and provided such defects are not due to abuse or decomposition by chemical or galvanic action.

ThiS expreSS warranTy iS in lieu OF and excludeS all OTher warranTieS, guaranTeeS, Or repreSenTaTiOnS, expreSS OF implied. There are

nO implied warranTieS OF merchanTaBiliTy Or OF FiTneSS FOr a parTicular purpOSe. The Seller assumes no responsibility for repairs made on the

Seller’s equipment unless done by the Seller’s authorized personnel, or by written authority from the Seller. The Seller makes no guarantee with respect to material

not manufactured by it.

NOTE: AFTER COMPLETING REPAIRS,

CHECK DISCHARGE TEMPERATURE.

RESET IF NECESSARY.

WARNING: FAILURE TO PERFORM THIS

OPERATION COULD RESULT IN UNSAFE

DISCHARGE TEMPERATURE, WHICH MAY

CAUSE INJURY OR DEATH.

!