Series RSS/F

Page 6

9260-060-en

Revision 03

TM 7168

Edition 06/2008

1.5 Flow values, kv100 (Cv)

V- and Parabolic plugs

Nominal

size

Kv100

Cv

Seat -

in mm

[

mm] [inch]

8

8

8

8

8

8

14 14 14 14 14 14 15 20 25

15

½“

m

3

/h

USgpm

0,05
0.06

0,10
0.12

0,20
0.23

0,50
0.58

0,80
0.93

2
2,3

4
4,7

20

¾“

m

3

/h

USgpm

0,05
0,06

0,10
0.12

0,20
0.23

0,50
0.58

0,80
0.93

2
2,3

4
4,7

25 1“

m

3

/h

USgpm

2
2,3

0,05
0,06

0,10
0.12

0,20
0.23

0,50
0.58

0,80
0.93

1,20
1.40

4
4,7

7
8,2

11
12,8

Nominal

size

Kv100

Cv

Seat -

in mm

mm] [inch]

15 20 25 30 40 50 65 80 96

40 1½“

m

3

/h

USgpm

4
4,7

7
8,2

11
12,8

15
17,5

28
32,6

50 2“

m

3

/h

USgpm

7
8,2

11
12,8

15
17,5

28
32,6

42
48,9

65 --

m

3

/h

USgpm

7
8,2

11
12,8

15
17,5

28
32,6

42
48,9

80 3“

m

3

/h

USgpm

15
17,5

28
32,6

42
48,9

65
75,7

100
117

100 4“

m

3

/h

USgpm

42
48,9

65
75,7

100
117

155
180

U-Plugs

DN

Seat -

in mm [inch]

[mm] [inch]

80 [3.15]

96 [3.78]

80

3"

90 m

3

/h

105 USgpm

100

4"

90 m

3

/h

105 USgpm

135 m

3

/h

157 USgpm

Notes:
The next lower kv100/Cv value can also be achieved
with special plugs without changing the seat .
This is important if the kv100/Cv value is subsequently
changed as only the plug then has to be replaced.
Conversion into Cv (US gpm) = kv100 x 1,165.

1.6 Cavitation coefficient z

K

v

/ K

v100

= 75%

DN

Seat -

in mm

[mm]

[inch

]

8

14

15 20 25 30 40 50 65 80 96

15 ½“ 0,60 0,60 0,60

20 ¾“ 0,60 0,60 0,60

25 1" 0,60 0,60 0,60 0,60 0,60

40 1½"

0,60 0,60 0,60 0,55 0,50

50 2"

0,60 0,60 0,55 0,50 0,40

65 --

0,60 0,60 0,55 0,50 0,40

80 3"

0,55 0,50 0,45 0,32 0,30

100 4"

0,47 0,33 0,30 0,26

v

1

F

p

p

p

X

=

X

F

= Differential pressure ratio

p

= Differential pressure inlet/outlet

p

1

= Absolute pressure at inlet

p

v

= Vapour pressure at operating temperature

X

F

z

: non-critical conditions

X

F

1,4 x z : tolerable cavitation

X

F

> 1,4 x z : inadmissible cavitation