tekmar 356 Mixing Control User Manual

Page 3

Advertising
background image

Copyright © D 356 -0

9/08

3 of 16

Sequence of Operation

Section A

General Operation

Page 3-4

Section B

Mixing

Page 4-6

Section C

Boiler Operation

Page 7

Section A — General Operation

POWERING UP THE CONTROL

When the Mixing Control 356 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software
version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the
current outdoor air temperature.

Item

{

Terminal Unit

VIEW ADJUST

TARGET

INDR

DSGN DIFF

BOIL

MIX

OUTDR

ROOM WWSD

°F

°C

MAX

MIN

Return

Mixing

Demand

Supply

% Out

10 30 50 70 90

Number Field

Displays the current value
of the selected item

Buttons

Selects Menus, Items
and adjusts settings

Menu Field

Displays the
current menu

Status Field

Displays the
current status of
the control’s
inputs, outputs
and operation

Item Field

Displays an
abbreviated
name of the
selected item

Symbol Description

Display

Burner
Displays when the boiler relay is turned on.

°F, °C

°F, °C

Displays the unit of measure that all of the
temperatures are to be displayed in the control.

Pointer
Displays the control operation as indicated by
the text.