tekmar 356 Mixing Control User Manual

Page 4

Advertising
background image

Copyright © D 356 -0

9/08

4 of 16

OPERATION

The 356 uses a variable speed injection pump to control the supply water temperature to
a hydronic system. The supply water temperature is based on either the current outdoor
temperature, or a fixed setpoint.

Outdoor Reset

When the outdoor design (OUTDR DSGN) setting is not set to OFF, the 356 calculates
a mixing supply temperature based on the current outdoor air temperature and the

Char-

acterized Heating Curve settings.

Setpoint Control

When the outdoor design (OUTDR DSGN) setting is set to OFF, the 356 supplies a fixed
mixing supply temperature equal to the MIX TARGET setting. An outdoor sensor is not
required during this mode of operation.

VARIABLE SPEED INJECTION

A standard wet rotor circulator is connected to the 356 at the back of the control. The 356
increases or decreases the power output to the circulator when there is a mixing demand.
The circulator speed varies to maintain the correct mixed supply water temperature at the
mix sensor. For correct sizing and piping of the variable speed injection driven circulator,
refer to essay E 021. A visual indication of the current variable speed output is displayed in
the LCD in the form of a horizontal bar graph.

BOILER PROTECTION (BOIL MIN)

The 356 is capable of providing boiler protection from cold mixing sys-
tem return water temperatures. If the boiler sensor temperature is cooler
than the BOIL MIN setting while the boiler is firing, the 356 reduces the
output to the variable speed injection pump. This limits the amount of
cool return water to the boiler, and allows the boiler temperature to re-
cover. This feature can only be used if a boiler sensor is installed.

EXERCISING

The 356 has a built-in exercising function. If the pump has not been operated at least once every 3 days, the control turns on the
output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity.

Note: The exercising function does not work if power to the control or pump is disconnected.

FACTORY DEFAULTS

The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To
fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal
unit number will flash when selected in the ADJUST menu.

To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while
simultaneously holding the

Item and buttons. The terminal unit number should now be displayed constantly in the LCD rather

than flashing.

Section B: Mixing

Section B1

General

Section B2

Installer

Section B3

Advanced

Section B1: General

MIXING DEMAND

A mixing demand is required in order for the 356 to provide heat. A mixing demand is
generated by connecting terminal

T(7) to terminal C-(9) through a switching device. Once

the switching device closes, the

Mixing Demand pointer is displayed in the LCD. The 356

calculates a MIX TARGET supply temperature based on the outdoor air temperature and
settings. If required, the 356 operates the boiler in order to provide heat to the variable
speed injection pump.

% Out

Current output of

variable

speed injection pump

30

10

70

50

90

Zone Valve Motor

End Switches

M

M

To control

C
R

Mixing

sensor

Boiler return

sensor

Boiler supply

sensor

or

Outdoor Design

Increasing W

ater

T

emperature

Design Supply

Decreasing Outdoor Temperature

Terminal Unit

Indoor Design

Advertising