SPECIFICATIONS
2.06 Specifications & Electrical Requirements
Maximum OCV (U
0
)
380 vdc
Maximum Output Current
200 Amps
Maximum Output Voltage
230 vdc
Duty Cycle Rating
100% @ 200A, 180vdc (32 kW),
@ 104F° (40°C) Ambient Temperature
Operating range
14°F to 122°F (-10°C to + 50°C)
Power Factor
0.70 @ 100 ADC Output
Cooling
Forced Air (Class F)
Ultra-Cut® 200 Power Supply Specifications
Input
Power Input
Current
Voltage
Freq.
3-Ph
3-Ph
Fuse (Amps)
Wire (AWG)
(Volts)
(Hz)
(kVA)
(Amps)
3-Ph
3-Ph
208
50/60
46
130
160
#1
230
50/60
49
125
150
#1
380
50/60
52
81
100
#4
400 (CE)
50/60
52
77
90
#4
460
50/60
59
75
90
#4
600
50/60
52
51
60
#6
* Suggested wire size based on United States NFPA 70 National Electrical Code 2005 edition
published by the National Fire Prevention Association.
Listings are from rable 400.5(B) for flexible cord of certain types rated for 75 deg. C in ambient
temperatures up to 30 deg. C. Using wires of lower temperature rating or different insulation
type may require larger wire size. Derate for higher ambient temperature.
Wire sizes are suggestions only. Always refer to your local and national codes that apply to
your location for correct wire sizes.
Ultra-Cut 200 Power Supply Electrical Inputs
Suggested Sizes (See Note)