INSTALLATION, OPERATION AND SETUP

3-2

Manual 0-5145

WARNING

The Fabricator 141i must be electrically connected by a qualified electrical trades-person. Damage to the

PCA (Power Control Assembly) could occur if 140 VAC or higher is applied to the Primary Power Cable.

WARNING

ELECTRIC SHOCK can kill; SIGNIFICANT DC VOLTAGE is present after removal of input power. DO NOT

TOUCH live electrical parts.

SHUT DOWN welding Power Source, disconnect input power employing lockout/tagging procedures. Lock-out/

tagging procedures consist of padlocking line disconnect switch in open position, removing fuses from fuse box,

or shutting off and red-tagging circuit breaker or other disconnecting device.
Electrical Input Requirements
Operate the welding Power Source from a single-phase 50/60 Hz, AC power supply. The input voltage must match

one of the electrical input voltages shown on the input data label on the unit nameplate. Contact the local electric

utility for information about the type of electrical service available, how proper connections should be made, and

inspection required. The line disconnect switch provides a safe and convenient means to completely remove all

electrical power from the welding power source whenever necessary to inspect or service the unit.
Do not connect an input (WHITE or BLACK) conductor to the ground terminal.
Do not connect the ground (GREEN) conductor to an input line terminal.
• Correctly installed, if necessary, by a qualified electrician.
• Correctly earthed (electrically) in accordance with local regulations.
• Connected to the correct size power point, fuse and primary supply lead based on Table 3-1. Refer to Table

3-1.

WARNING

An electric shock or fire hazard is probable if the following electrical service guide recommendations

are not followed. These recommendations are for a dedicated branch circuit sized for the rated output

and duty cycle of the welding Power Source.

50 / 60 Hz Single Phase Supply

Supply Voltage

115V AC

Input Current at Maximum Output

28.4 Amps

Maximum Recommended Fuse* or Circuit Breaker Rating

*Time Delay Fuse, UL class RK5. Refer to UL248

Maximum Recommended Fuse^ or Circuit Breaker Rating

^Normal Operating , UL class K5. Refer to UL248

30 Amps

30 Amps

Single Phase Generator Requirement

5 KW

Minimum Recommended Input Cable Size

12AWG

Maximum Recommended Input Cable Length

10ft (3m)

Minimum Recommended Grounding Cable Size

12AWG

Table 3-1: Electrical Service Guide