Feed Wiring (Section A)

Feed Wiring for MLO (left) and MCB (right) Applications

Refer to the following table for information on wiring the feed to the panel.

Feed Wire Information

120 Volt Models

277 Volt Models

TERMINAL CONNECTOR

MAX

WIRE RANGE

TORQUE Max

Current

CONNECTOR MAX

WIRE RANGE

TORQUE

Max

Current

Neutral and
Main Lugs

10-2/0 AWG (CU) or
6-2/0 AWG (AL)

6 - 300 kcmil (CU or AL)

15 lb-ft
(20.3 Nm)

21 lb-ft
(28.5 Nm)

6-350 kcmil (CU or AL)
1/0-750 kcmil (CU or AL)

275-300 lb-in
(31.1-33.9 Nm)

Neutral Bus

14-10 AWG(CU) or
12-10 AWG (AL)
8 AWG (CU or AL)

6-4 AWG (CU or AL)

20 lb-in
(2.3 Nm)
25 lb-in
(2.8 Nm)
35 lb-in
(4.0 Nm)

225

Amps

14-6 AWG (CU or AL)

14-2/0 AWG (CU or AL)

24-35 lb-in
(2.7-4.0 Nm)
40-50 lb-in
(4.5-5.6 Nm)

250

Amps

Use copper or aluminum conductors only – rated 75

°C.

WARNING: Failure to properly tighten lugs may result in poor electrical connection and overheating of the terminals.