Power Switching

CRESTRON GREEN LIGHT™

The GLXP-DIMFLV8 also requires wiring the terminals for 0-10 VDC control wire. Refer to the following
diagram when connecting the dimmable ballast. Each control wire terminal accepts one 12 – 28 AWG wire.

0-10 VDC Control Wiring for GLXP-DIMFLV8 Only

TO + ON 4-WIRE LOADS (PURPLE)

TO - ON 4-WIRE LOADS (GRAY)

2. Test the circuit for electrical faults by turning on each circuit breaker, checking that the breakers do not

trip, and that power is delivered to the proper loads.

3. Turn off the circuit breaker(s) and remove all jumpers.

4. Turn on the circuit breakers.

Control Wiring (Section C)

The bottom of the cabinet contains Cresnet

®

connections for interfacing to the rest of the Crestron

®

control system.

It also provides an override input which can be tied to devices such as the GLS-PLS-120/277 phase-loss sensor, or
other devices that provide a dry contact closure (manual switch, fire alarm relay, etc.).

NOTE: Interface connectors for NET (x2), POWER (x1), and OVERRIDE (x1) ports are provided.

Wire Gauge and Torque Values

TERMINAL CONNECTOR

MAX

WIRE RANGE

TORQUE STRIP

LENGTH

NET 12

AWG

4.43 lb-in

(0.5 Nm)

1/4”

(6 mm)

POWER

26-12 AWG

4.43 lb-in

(0.5 Nm)

1/4”

(6 mm)

OVERRIDE 26-12

AWG

4.43 lb-in

(0.5 Nm)

1/4”

(6 mm)

8

CRESTRON GREEN LIGHT Power Switching

Installation Guide – DOC. 6672B