INSTALLATION AND OPERATING INSTRUCTIONS (continued)

supervisory controls. GNB recommends a 7 hours on-charge-

17 hours off-charge control for these 24-hour periods.

7. SAFETY

• Warning: Risk of fire, explosion, or burns. Do not disassemble,

heat above 38 degrees Celsius, or incinerate.

• Wear appropriate safety equipment when working around

electrically live batteries.

• The ELEMENT

®

battery can emit hydrogen gases under

some abnormal charging conditions. Whenever possible,

charge in a well-ventilated area and keep open flames

away from batteries. However, normal warehouse

ventilation is adequate for normal ELEMENT

®

usage.

• Lift batteries with a hoist, crane, lift truck, or similar

equipment; move batteries on trucks, conveyors, or rollers.

Make sure equipment is of ample strength and properly

installed. Be sure to place a rubber mat or similar

insulating material across tops of batteries without covers

when handling. This will prevent accidental shorts.

• Disconnect battery from the truck when performing

maintenance and repair on motor or electrical system.

• Open, or “break” battery circuit before attempting repairs

to charging plug or receptacles.

• Familiarize yourself with batteries and rules for charging

and handling. Contact your local GNB representative for

information.

• Assign battery and charger care to properly trained

personnel. Review your company safety regulations, and

familiarize yourself with industry and government

guidelines (OSHA, ANSI, etc.) to help reduce personnel

accidents and equipment damage.

8. OPERATION

Batteries are rated in ampere-hour and are selected to

perform a specific workload within an established period of

time. Increasing the work load or time period could result in

over discharging, thus shortening battery life. In general, all

lead-acid batteries should not be discharged to more than

80% of its six-hour rated capacity. ONE BATTERY IS
REQUIRED PER TRUCK PER EIGHT-HOUR SHIFT.

If a

lift interrupt is used or installed on the lift truck, a minimum

interrupt voltage of 1.86 VPC (under load), 2.02 VPC (open

circuit) multiplied by the number of cells, should be set to

avoid overdischarge of the battery.

Since ELEMENT

®

is a VRLA battery, it’s state of charge cannot

be approximated by specific gravity. However, average cell

voltage (Volts per Cell) with the battery under load can be used

to approximate the battery depth of discharge as shown in

Figure 1. Alternatively, the battery at 80% depth of discharge

will have an open circuit voltage equal to 2.02 VPC multiplied

by the number of cells in the battery.

9. BATTERY DISCHARGE ALARM/MONITORS

Your ELEMENT

®

battery is equipped with a Battery Discharge

Alarm to protect your ELEMENT

®

battery from over-discharge.

An intermittent 80-db alarm will start to sound whenever the

battery's voltage drops to or below the alarm reference

voltage for a fixed period of time. The alarm will stop if and

when the battery's voltage recovers to above the alarm

reference voltage within a fixed period of time. The battery is

at 80% depth of discharge when the alarm sounds

continuously. As soon as the alarm begins to sound

continuously, the battery should be completely recharged

using an approved charger and proper charging procedures.
Batteries may be equipped with monitoring devices by GNB.

Damage to or tampering with these devices shall void all

warranties. Any addition of monitoring devices affixed to the

battery, not authorized in writing by GNB, shall void all

warranties.

10. 48 VOLT ELEMENT

®

BATTERIES

Your 48 volt ELEMENT

®

battery may be equipped with an

active cooling system. This will be evident by two fan

cutouts on the battery cover and by "81" at the end of the

battery part number. The following special considerations

apply:
1. The fans will only operate when the battery is on charge

or during the cool-down period (at or above fully charged

open circuit voltage). The fans will not operate when the

battery is plugged into the lift truck. If the fans continue

to operate when the battery is plugged into the lift truck,

contact your local GNB service representative

immediately at 1-888-563-6300.

2. 48 volt ELEMENT

®

batteries equipped with the active

cooling system must be removed from the lift truck for

charging, and have a minimum of 6 inches of clearance

on all sides of the battery for proper airflow.

Deviations from the proper operating instructions for 48 volt

ELEMENT

®

batteries will void the warranty. Additional

information and assistance can be obtained by contacting

your local sales representative by calling 1-888-563-6300.

THE ELEMENT

®

BATTERY SHOULD NOT BE

DISCHARGED BELOW 1.86 VPC (UNDER LOAD), 2.02
VPC (OPEN CIRCUIT) (80% DEPTH OF DISCHARGE)

ADJUST LIFT INTERRUPT SETTING ON LIFT TRUCK TO
A MINIMUM INTERRUPT VOLTAGE OF 1.86 VPC (UNDER
LOAD), 2.02 VPC (OPEN CIRCUIT) MULTIPLIED BY THE
NUMBER OF CELLS FOR ELEMENT

®

BATTERIES

FIGURE 1 - ELEMENT

®

DISCHARGE CURVE