Operating the at10.1 – Exide Technologies Section 94.30 User Manual

Page 47

Advertising
background image

OPERATING THE AT10.1

43

Exercise front

panel controls

•

Switch from float to equalize, then back
to float.

•

Turn off the dc circuit breaker.

E 07 may

appear on display (requires at least 5% of
rated output current). Reset breaker.

o

OK

o

OK

•

Cycle through meter modes.

o

VOLTS

OK

o

AMPS

OK

o

HOURS

OK

•

Cycle through equalize methods.

o

MANUAL TIMER

OK

o

MANUAL EQLZ

OK

o

AUTO EQLZ TIMER

OK

•

Turn off ac circuit breaker. The

AC

INPUT FAILURE indicator should light.
Reset breaker.

o

Alarm OK

Check voltage

and alarm
settings

•

Use

EDIT/ENTER

key to scroll through

settings. See page 30.

o

FLOAT

OK

o

EQUALIZE

OK

o

HVDC

alarm OK

o

LVDC

alarm OK

Current limit Adc

Final checks

•

Make sure plexiglas safety cover is in
place.

•

Restore charger to normal operation.

•

Close latch on front panel.

o

OK

o

OK

o

OK

Step

(optional features)

Instructions

Results

Test auxiliary
alarm relays

•

Press

LAMP TEST

key and hold for 4

seconds. Alarm relays will transfer.

o

OK

Check
integrity of

remote wiring

•

Remote sense wiring. See page 16.

•

Temperature compensation wiring. See
page 20.

•

Temperature compensation probe. See
page 20.

o

OK

o

OK

o

OK

Final checks

•

Close padlock or key lock.

o

OK

A downloadable worksheet of this Preventive Maintenance Procedure (

JD0064-00

)

is available online (

http://www.ATSeries.net/PDFs/JD0064-00.pdf

)

.