1 maintenance, 2 troubleshooting – Bio-Rad PowerPac™ Basic Power Supply User Manual

Page 13

Advertising
background image

Section 4
Maintenance and Troubleshooting

4.1 Maintenance

The PowerPac Basic requires little maintenance to assure reliable operation. To clean the

case, first unplug the power supply. Use a damp cloth to wipe down the outer case.

4.2 Troubleshooting

Problem

Cause Solution

No display/lights/fan

1. No AC power.

1. Check if PowerPac Basic is

2. Blown fuse.

unplugged, or problem with AC

3. Power switch

power source, or power switch is in

exercised rapidly to

off position.

the on and off

2. Replace fuse. See section 4.3 for

positions.

details.

3. The unit needs to be reset. Turn

power switch to the off position,
wait 5–10 seconds, then turn
power switch to the on position to
resume
normal operation.

Repeated blown fuses Hardware failure

Contact Bio-Rad Technical Resources.

Leads from cell are

Output terminals for the

Use the PowerPac Adaptor, which

not long enough to fit PowerPac Basic are

accommodates most standard 4 mm

output jacks

recessed 16 mm to

banana plugs, to make a secure

meet safety regulations.

electrical connection.

Some leads are not
long enough to make

Note: Use of the PowerPac Adaptor

electrical connection.

voids EN61010 safety provisions.

E1 error code

No load detected

Verify all electrical connections.

displayed

Verify buffer levels where appropriate.

Instrument not
connected to PS

The current load is
below 4mA

E2 error code

Over current (load

Check for and correct any short circuit

displayed

current greater then

or excessive load problem. Excessive

400 mA)

load due to high buffer concentration
will require the buffer be remade.
Then,
• Press

key to resume the run or,

• To clear the error code, press any
key (other then

key).

E3 error code

Over voltage (load

Turn power supply off, then on to.

displayed

voltage over 300 V)

reset If problems persists, contact
Bio-Rad Technical Resources.

E5 error code

A power failure occurred during a timed run with Power Fail

Detection played

(PFd) activated, and run is completed. Power Fail detection (Pfd) is
de-activated after completion or termination of each run.

E6 error code

A power failure occurred during a timed run without Power Fail

displayed

Detection (PFd) activated, and run is not completed.

E7 error code

Power Failure occurred during an untimed run or the power switch

displayed

was turned off before pressing stop,. and run is not completed.
Power Fail detect (Pfd) cannot be activated for untimed runs.

7

Advertising