Example - nec – Cooper Bussmann CT02MAN User Manual

Page 52

Advertising
background image

50

Cooper B-Line, Inc

Cable Tray Manual

Appendix Sheet 6

Example - NEC

®

Section 392.9(B)

Cable Tray containing Type ITC or Type PLTC Cables

50% of the cable tray useable cross sectional area can contain type PLTC cables

4 inches x 6 inches x .050 = 12 square inches allowable fill area.

2/C - #16 AWG 300 volt shielded instrumentation cable O.D. = 0.224 inches.

Cross Sectional Area = 0.04 square inches.

Notes:

1. The cable sizes used in this example are a random selection.

2. Cables - copper conductors with PVC insulation, aluminum/mylar shielding, and PVC jacket.

6" Usable Cable Tray Width

4" Usable

Cable Tray

Depth

Cross Section Of The Cables And The Cable Tray

= 300 cables can be installed in this cable tray.

12 sq. in.

0.04 sq. in./cable

= 11.54 rows can be installed in this cable tray.

300 cables

26 cables/rows