Cable tray sizing flowchart, Start here sizing cable tray per nec 392 – Cooper Bussmann CT02MAN User Manual

Page 54

Advertising
background image

52

Cooper B-Line, Inc

Cable Tray Manual

CABLE TRAY SIZING FLOWCHART

Appendix Sheet 8

392.12

W ≥ Sd

(single layer)

392.3(B)(1)(a)

Not permitted

by the NEC

®

392.10

Not

recognized by

the NEC

®

392.10(B)

W ≥ Sd

392.10(A)(1)

W ≥ Sd

392.10(A)(2)

W ≥ A/1.1

Note: The value “A”

only applies to cables

250 up to 1000kcmil.

The value “sd” only

applies to 1000 kcmil

and larger cables.

Note: Use when mixing

250 thru 1000 kcmil

cables with cables larger

than 1000 kcmil.

392.10(A)(3)

392.10(A)(4)

W ≥ Sd

(9” max. RS)

2000V

or less

cables

Multi-

conductor

cables

S/C 1/0

or larger

Ladder

or Vented

Trough

Tray

S/C

1000

kcmil or

larger

S/C
250

kcmil up to

1000

kcmil

S/C

250 kcmil

and

larger

S/C 1/0

thru 4/0

Vented

Channel

Tray

Solid

Bottom

Tray

W ≥ A/1.1 +Sd

No

No

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Continued

on next

page

Yes

Legend

W = Cable Tray Width

D = Cable Tray Load Depth

Sd = Sum of Cable Diameters

A = Sum of Cable Areas
S/C = Single Conductor

M/C = Multiconductor Cables

RS = Ladder Rung Spacing

Start

Here

Sizing Cable Tray Per NEC 392