Termination clearances, Rear venting applications – Vermont Casting DBR36 User Manual

Page 10

Advertising
background image

- 10 -

Fig. 13

*IMPORTANT* DIRECT THROUGH SIDEWALL

Note:

Vent Starter Kit Model 7DVRVT must be

used in straight out the wall rear vent applications.

Maximum Vent Length .......................... 20" (508mm)- Fig. 14

Fig. 14

REAR VENTING APPLICATIONS

Note: It is not necessary to seal the vent pipe joints for any straight out the wall rear vent applications.

Minimum clearance
between vent pipes and
combustible materials is
one (1") inch (25 mm) on
sides and bottom and two
(2") inch (50 mm) on top.

When vent termination
exits through foundation
less than 20" (508mm)
below siding outcrop, the
vent pipe must flush up
with the siding. A 7DVSS
must also be used.

TOP VIEW

20" (508mm)

TOP VIEW

CROSS CORNER VENT

TO THE LEFT.

20"
508mm

45

°

TOP VIEW

CROSS CORNER VENT

TO THE RIGHT.

20"
508mm

45

°

;;;;

;;

;

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

A =
Combustible
6"(152mm)

Noncombustible
2"(50mm)

B =
Combustible
6"(152mm)

Noncombustible
2"(50mm)

;

;;

A

;;

;;

;;

Balcony -
with no side wall

G =
Combustible&
Non-Combustible
12"(305mm)

G

Balcony -
with perpendicular side wall

H = 24"(610mm)

J = 20"(508mm)

H

J

B

Recessed Location

C = Maximum depth of 48"
(1219mm) for recessed
location.

D = Minimum width for back wall
of a recessed location.
Combustible 38"(965mm)
Noncombustible 24"(610mm)

E = Clearance from corner in
recessed location.
Combustible 6"(152mm)
Noncombustible 2"(50mm)

;;;

C

D

C

E

V

V

Combustible &
Non-Combustible

V

V

V