Dell UPS 3750R User Manual
Page 63
63
MIB Objects
|
Table 11. IETF UPS MIB Objects (continued)
Variable Name and Relative XML Object Path
Variable Unit
Variable Type
OID
upsConfigInputVoltage
UPS.Flow[1].ConfigVoltage
1.9.1
Integer
V
upsConfigInputFreq
UPS.Flow[1].ConfigFrequency
1.9.2
Integer
0.1 Hz
upsConfigOutputVoltage
UPS.Flow[4].ConfigVoltage
1.9.3
Integer
V
upsConfigOutputFreq
UPS.Flow[4].ConfigFrequency
1.9.4
Integer
0.1 Hz
upsConfigOutputVA
UPS.Flow[4].ConfigApparentPower
1.9.5
Integer
VA
upsConfigOutputPower
UPS.Flow[4].ConfigActivePower
1.9.6
Integer
W
upsConfigLowBattTime
No Relative XML Object Path
1.9.7
Integer
Min
upsConfigAudibleStatus
UPS.BatterySystem.Battery.AudibleAlarmControl
1.9.8
Integer
—
upsConfigLowVoltageTransferPoint
UPS.PowerConverter.Output.LowVoltageTransfer
1.9.9
Integer
V
upsConfigHighVoltageTransferPoint
UPS.PowerConverter.Output.HighVoltageTransfer
1.9.10
Integer
V