Figure 7: edit scan settings  virtualization – Dell UPS 4200R User Manual

Page 9

Advertising
background image

Dell UPS Management Software: VMware vCenter Shutdown Scenarios

9

1. Install the MUMC client to the same Windows OS.

2. Login to the MUMC client (default admin/admin).

3. Navigate to Settings  Auto Discovery. Add the Dell UPS node (QuickScan or Range Scan).

Figure 5: MUMC client  Settings  Auto Discovery  Add Node

4. Right-click the UPS node and “Set Node Access Parameters” (default is admin/admin).

5. Navigate to Settings  System  Edit Modules Settings, and enable the Virtualization Module.

Note: Only enable the “Shutdown” module if you want the computer hosting the MUMC client
to shut down in the event of a power failure. Once the computer hosting the MUMC client has
shut down, it is no longer able to control hypervisor function, so care take care to ensure that
the computer hosting the MUMC client is shut down in the last possible moment after all
hypervisor actions have been taken.

Figure 6: MUMC client  Settings  System  Modules Settings  Edit Scan Settings

Figure 7: Edit Scan Settings  Virtualization