Cabling Instr uctions for the –48 VDC

1-3

To construct the DC input power cable, perform the following steps:

1

Strip the insulation from the ends of the six DC power wires, exposing approximately

4.5 mm (0.175 inches) of copper wire.

2

Using a hand-crimping tool, crimp a connector contact to each DC power wire.

3

Slide a piece of heat-shrink tubing over the DC power cable.
The heat-shrink tubing should be approximately 3.175 cm (1.25 inches) in length.

4

Insert the three black –48 VDC wires into connector housing positions 2, 3, and 6 (see

Figure 1-1 and Table 1-1).

5

Insert the three red –48 VDC return wires into connector housing positions 1, 4, and 5

(see Figure 1-1 and Table 1-1).

6

Slide the heat-shrink tubing over the DC power cable so that it overlaps the connector

housing by at least 6.35 mm (0.25 inches).

7

Using a heat gun, shrink the tubing around the cable and connector housing.

F i g u r e 1 - 1 .

C o n n e c t o r H o u s i n g

Ta b l e 1 - 1 .

C o n n e c t o r H o u s i n g P i n A s s i g n m e n t s

Pin

Description

Wire Color and Size

1

–48 VDC return

Red 16 AWG

2

–48 VDC

Black 16 AWG

3

–48 VDC

Black 16 AWG

4

–48 VDC return

Red 16 AWG

5

–48 VDC return

Red 16 AWG

6

–48 VDC

Black 16 AWG

1

2

3

6

5

4

front view

0R216bk0.book Page 3 Monday, April 8, 2002 1:25 PM