Culligan Soft-Minder Twin

®

Softeners

Table 2 - Salt Dosage vs. Capacity vs. Timer Settings

Unit

Exchange Capacity @ Salt
Dosage Per Regeneration

Refill Time

(Minutes)

DLFC

BLFC

Injector

Flow

Number

Flow

Color

Number

SM-61

13,760 gr @ 3.3 lb

4

2 gpm

3

0.25 gpm

RED

0

27,848 gr @ 9.3 lb

6

0.5 gpm*

WHITE*

1

32,932 gr @ 15.0 lb

10

SM-91

21,193 gr @ 5 lb

4

2 gpm

3

0.50 gpm

WHITE

1

42,890 gr @ 14 lb

9

50,732 gr @ 22.5 lb

15

* Shipped inside control valve

Gallon Settings

The model 9000 valve regenerates with soft water from the other tank, you must subtract the water used for regeneration.If 1000

gallons are available then you must subtract the regeneration water used from the total water available.

If there are 1000 gallons available subtract the regeneration water used from total water available.

1000 gallons available – 51 gallons used = 949 gallons returning (in regeneration)

The meter wheel should be set at 950 gallons. Lift the inner dial of the meter program wheel (Fig. 4) so that it rotates freely.

Position the white dot opposite the 950 gallon setting.

Insert meter cable into the meter.

Check bypass.

Plug in unit.

Sanitizing Procedure

A water softener in daily use on a potable water supply generally requires no special attention other than keeping the salt tank

filled. Occasionally, however, a unit may require sanitization under one of the following conditions:

At start-up time.

After standing idle for a week or more.

On private supplies, the appearance of off-tastes and odors, particularly if musty or “rotten egg” (caused by harmless sulfate-

reducing bacteria).

Note: If the water supply contains iron, regenerate the softener before sanitizing to remove iron from the resin.

Caution!

Hazard from toxic fumes! Chlorine bleach and common iron control chemicals may generate toxic fumes

when mixed.
• If the unit uses culligan Sofner-Gard

®

or other compounds containing sodium hydrosulfite, sodium bisulfite, or

any other reducing agent, disconnect the device feeding the chemical(s) and manually regenerate the unit before

sanitizing.

Do not use this procedure if the softener salt contains iron control additives.