Upgrading the firmware – Dell Metered PDU LCD User Manual

Page 10

Advertising
background image

10

|

Network Upgrades for NMC and MCU Firmware

Upgrading the Firmware

These instructions describe the network flash upgrade procedure in the following sequence:

S

Preparing the rPDU for the upgrade

S

Accessing the network upgrade user interface

S

Selecting upgrade settings

S

Identifying the rPDU to upgrade

S

Selecting to upgrade either NMC or MCU firmware

S

Completing the upgrade process

NOTE:

If power to the rPDU is interrupted at any time during the upgrade, check each circuit breaker and reset if necessary.

To prepare the rPDU for the network NMC or MCU firmware flash upgrade, perform the following:

1

Verify that the rPDU you intend to upgrade is powered up and properly connected to the PC USB port using the
Ethernet cable (see Figure 4).

2

Execute the upgrade.exe program. The Upgrade -- PDU Upgrade Utility window displays.

3

Select the IPv4 or IPv6 radio button to specify the version of IP addresses you want to retrieve (see Figure 5).

Figure 5. Selecting IPv4 or IPv6