MIB Objects

|

Table 11. IETF UPS MIB Objects (continued)

Variable Name and Relative XML Object Path

Variable Unit

Variable Type

OID

upsBypassNumLines

No Relative XML Object Path

1.5.2

Integer

—

upsBypassVoltage

UPS.PowerConverter.Input[2].Voltage

1.5.3.1.2

Integer

V

upsBypassCurrent

UPS.PowerConverter.Input[2].Current

1.5.3.1.3

Integer

0.1A

upsBypassPower

No Relative XML Object Path

1.5.3.1.4

Integer

W

upsAlarmsPresent

No Relative XML Object Path

1.6.1

Gauge

—

upsAlarmTable

No Relative XML Object Path

—

—

—

upsAlarmBatteryBad

UPS.PowerSummary.PresentStatus.NeedReplacement

1.6.3.1

—

—

upsAlarmOnBattery

UPS.PowerSummary.PresentStatus.Discharging

1.6.3.2

—

—

upsAlarmLowBattery

UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit

1.6.3.3

—

—

upsAlarmDepletedBattery

Relative XML Object Path not implementated

1.6.3.4

—

—

upsAlarmTempBad

UPS.PowerSummary.PresentStatus.OverTemperature

1.6.3.5

—

—

upsAlarmInputBad

UPS.PowerConverter.Input[1].PresentStatus.VoltageOutOfRange

1.6.3.6

—

—

upsAlarmOutputBad

Relative XML Object Path not implementated

1.6.3.7

—

—

upsAlarmOutputOverload

UPS.PowerSummary.PresentStatus.Overload

1.6.3.8

—

—

upsAlarmOnBypass

UPS.PowerConverter.Input[2].PresentStatus.Used

1.6.3.9

—

—

upsAlarmBypassBad

UPS.PowerConverter.Input[2].PresentStatus.Good

1.6.3.10

—

—

upsAlarmOutputOffAsRequested

Relative XML Object Path not implementated

1.6.3.11

—

—