Dell UPS Management Software: Common Software Installation Scenarios
23
F.
Load Segment:
Only use this variable if you are using Load Segments to preferentially
control hardware startup/shutdown behaviour (e.g. servers and storage on separate
profiles).
G.
Master - Shutdown Duration:
The time (in seconds) it takes for the host to shut
down (including any vMotion activities). Make sure that the time between
“
Maintenance Timer
” and “
Master - Shutdown After
” gives enough time for any
VM migrations to occur. Otherwise the migrations will fail and the VM will shut down on
the original host location.
H.
Master - Shutdown After:
The time (seconds) following a power failure that the
shutdown command should be sent to the host.
Figure 29: UPS Battery capacity over time