Environmental

Maximum Shock

Operating

One shock pulse (one pulse each side of the system) of 31 G for 2.6 ms in
the operational orientation.

Non-operating

Six consecutively executed shock pulses in the positive and negative x, y,
and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Six consecutively executed shock pulses in the positive and negative x, y,

and z axes (one pulse on each side of the system) of 32 G faired square

wave pulse with velocity change at 270 inches/second (686 centimeters/

second).

Altitude

Operating

–16 m to 3048 m (10,000 ft).

NOTE: For altitudes above 950 m (3,117 ft), the maximum operating
temperature is derated 1°C/300 m (1 ºF/547 ft).

Storage

–15.2 m to 12,000 m (–50 ft to 39,370 ft)

Airborne Contaminant Level

Class

G1 as defined by ISA-S71.04-1985

Particulate Contamination

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and
gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits
specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for
you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of
environmental conditions will be the responsibility of the customer.

Air Filtration

NOTE: Applies to data center
environments only. Air filtration
requirements do not apply to IT
equipment designed to be used
outside a data center, in
environments such as an office or
factory floor.

Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a
95% upper confidence limit.

NOTE: Air entering the data center must have MERV11 or MERV13
filtration.

Conductive Dust

NOTE: Applies to data center and
non-data center environments.

Air must be free of conductive dust, zinc whiskers, or other conductive
particles.

Corrosive Dust

NOTE: Applies to data center and
non-data center environments.

Air must be free of corrosive dust.

Residual dust present in the air must have a deliquescent point less

than 60% relative humidity.

Gaseous Contamination

NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.