Standing Pilot Ignition System Troubleshooting Chart

Pilot lit?

Main

burners

light?

Y

Turn control on
gas valve to
PILOT. Depress
red button and
light pilot. Hold
button for at
least one
minute.

Does pilot

light?

N

*Pilot tubing
blocked, kinked
or leaking

*Pilot orifice
blocked

*Gas line not
purged of air

*Pilot improperly
adjusted.

Line pressure

within the range

indicated on

boiler's rating

plate?

Consult gas
supplier.

Does pilot

stay lit?

*Defective thermocouple

*Pilot improperly
adjusted

*Pilot tube blocked, kinked, or
leaking

*Pilot orifice partially plugged

Y

N

N

Y

N

Turn control
on gas valve
to ON.

Y

END

*Defective gas
valve

Y

START

(24 VOLTS PRESENT ACROSS TH AND TR

ON GAS VALVE, BUT MAIN BURNERS DO

NOT LIGHT)

Ensure knob
on gas valve is
set to ON

*Loose
thermocouple
connection at
gas valve.

*Defective
thermocouple.

*Condensation
quenching pilot.

*Low line
pressure.

N

Y

N

Does pilot

stay lit when

red button is

released?

Disconnect
thermocouple from
gas valve. Connect a
volt meter to the
thermocouple. Light
the pilot and hold
down the red button
while reading the
voltage across the
thermocouple.

Is voltage at

least 18mV?

*Loose or defective
thermocouple
connection at gas valve

*Defective gas valve

Y

N

Caution: Read page 36 before

attempting to use this chart