Chateau, Vertical through-the-roof installation – Vermont Casting ChateauTM DVT38IN User Manual

Page 23

Advertising
background image

23

Chateau™

20011956

Max. 20' (6 m)

Max. Height

40' (12 m)

Min. Height

20' (6 m)

FP1244a

through the roof

max/min dims

4/03

Pipe Straps Every 3’

(914mm)

FP1244a

Fig. 29 Support straps for horizontal runs.

Up to two (2) 30° or 45° elbows may be used within
the horizontal run. For each 30° or 45° elbow used
on the horizontal level the maximum horizontal
length must be reduced by 18” (457 mm).

Example: Maximum horizontal length

0 x 30° or 45° elbows = 10’ (3 m)

1 x 30° or 45° elbows = 8’6” (2.6 m)

2 x 30° or 45° elbows = 7’ (2.1 m)

A minimum of an 12’ (3.7 m) vertical rise.

Two sets of 30° or 45° elbows offsets within these
vertical installations. From 0 to a maximum of 8’ (2.4
m) of vent pipe can be used between elbows. (Fig.
30)

SKCS8 must be used to support offsets. (Fig. 33)
This application will require that you first determine
the roof pitch and use the appropriate starter kit.
(Refer to Venting Components List)

The minimum height of the vent above the highest
point of penetration through the roof is 2’ (610 mm).
(Fig. 34)

Vertical Through-the-Roof Installation

1

2

3

4

Max. 8' (2.4m)

FP1245a

through the roof

90 & 45 degree

FP1245a

Fig. 30 Typical offset application.

1 + 2 + 3 + 4 = 270°

Minimum 2’ (610mm)

Before Any Elbow

1. Locate your fireplace.
2. Plumb to center of the (8”) flue collar from ceiling

above and mark position.

3. Cut opening equal to 14¹⁄₂” x 14¹⁄₂” (368 x 368 mm).
4. Proceed to plumb for additional openings through

the roof. In all cases, the opening must provide a
minimum of 1¹⁄₂” (38 mm) clearance to the vent pipe,
i.e., the hole must be at least 14¹⁄₂” x 14¹⁄₂” (368 mm
x 368 mm).

5. Place fireplace into position.
6. Place firestop(s) SKFS2A or Attic Insulation Shield

AIS-SK into position and secure. (Figs. 31, 32)

7. Install roof support (Fig. 33) and roof flashing making

sure upper flange of flashing is below the shingles.

8. Install appropriate pipe sections until the venting is

above the flashing.

9. Seal around the pipe.
10. Add additional vent lengths for proper height. (Fig.

34)

Advertising