Caution – Carrier 48/50PG20-28 User Manual

Page 7

Advertising
background image

7

6. Slide the sampling tube collar over the sampling tube

until the tabs lock into the tube.

7. Slide sampling tube into smoke detector with eight slots.

Make sure sampling tube holes are aligned facing UP.

8. Insert plug into far end of the sampling tube.
9. Place rubber gaskets over each sampling tube on smoke

detector. (See Fig. 2.)

10. Remove one knockout from top of smoke detector.
11. Insert one end of RJ-45 wire harness through knockout

and wire to smoke detector as shown in Fig. 10.

12. Slide smoke detector into holes in fan side plate with

the terminal block at the top and secure using two,

8-18

3

/

4

-in. pan head screws (P/N AL56AU168). Replace

cover.

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage.
Do not overtighten the screws.

CAUTION

!

13. Attach cable to fan side plate using snap-in wire ties.

See Fig. 9 for clarification. Secure to center post.

14. Secure cable to back side of cable tray using three snap-in

wire ties.

15. In the Electrical/Compressor section, install snap bushing

in the center knockout underneath the terminal strips

lo-

cated in the bottom right-hand corner of control box.

16. Connect wires to terminal strips as shown in Fig. 6 for

ComfortLinkt units or Fig. 7 for Electro--Mechanical

Units.

NOTE: This step is not needed with 48/50PG Humidi--MiZert
units because they have plug 19 harness already installed in the
control box. The harness assembly part number 50TG403507
that came with the accessory is not used. Factory installed PL--19
can be located outside the contol box by its appropriate label. For
Humidi--MiZer smoke detector wiring refer to Fig. 8.

17. Remove cover from control module and remove knockout

from side of module nearest the RJ-45 connector.

18. Using

three

8-18

3

/

4

-in.

pan

head

screws

(P/N AL56AU168) screws, secure control module to com-
pressor partition above compressor B1/A2 location.

19. Connect PL-19 from control module to PL-19 from wir-

ing harness installed in Step 16.

NOTE: On 48PG Humidi--MiZer units, the control box harness
has a jumper plug attached. This needs to be disconnected so
PL--19 from the smoke detector can be snapped in.

20. Route cable from supply smoke sensor, along the outside

of the control box, through the control module knockout

and connect to the J1 RJ-45 connector.

21. Using wire ties, secure the wiring so it does not interfere

with unit operation.

22. Replace control module cover.
23. Restore power to the unit.
24. Configure ComfortLink controller as specified in Config-

uring the ComfortLink Controller below.

25. Perform Sensor and Controller tests. At a minimum, the

Magnet test should be performed to verify smoke detector
wiring.

26. Turn off power to the unit.
27. Reconnect the indoor fan plug and the limit switch wires if

applicable.

28. Close the indoor fan section door.
29. Restore power to the unit and check for alarms. Correct

any problems encountered.

30. Close Electrical/Compressor section door.

Sensor Installation (CRSMKSEN001A00)

When adding return smoke sensor to previously installed supply
smoke detector:

1. Open electrical/compressor section access door/panel.
2. Disconnect PL-19 from control module to terminal strip

by separating plug connectors.

3. Remove control module cover. Disconnect supply sensor

RJ-45 wire from control module.

4. Remove three screws attaching control module to com-

pressor partition and save screws for later use.

5. Remove control module from unit.
6. Slide feet of control module into receptacle on the return

sensor housing and secure from the backside using one

screw removed in Step 4. The J1 RJ-45 connector on sen-
sor should be nearest the control module. Knockout holes

should align. (See Fig. 11.)

7. Route short RJ-45 wire from J1 connector of sensor,

through knockout holes, and connect to J1 connector of
control module.

8. Follow steps 2-20 of instructions for installing return

smoke detector.

IMPORTANT: Step 15 requires connecting the supply smoke
sensor RJ--45 wire to connector J2 in the control module.
When adding supply smoke sensor to previously installed return
smoke detector:
Follow steps 1-14 and 19-29 from supply smoke detector

installation instructions.

CR

S