SMOKE DETECTOR

WIRE TIES

C07180

Fig. 9

--- Supply Smoke Detector Location and Wire Routing (Top View)

AS SHOWN TO

PLUG

ROUTE RJ-45 HARNESS ALONG

SUPPLY SMOKE DETECTOR

THRU BOX, AND OUT

SMOKE POWER HARNESS

PUNCH OUT KNOCK OUT

INSTALL CONTROL
MODULE HERE
USING THREE SCREWS

RJ-45 HARNESS

CUT TAPE BEFORE

INSERTING SMOKE DETECTOR.

C07181

Fig. 10

--- Supply Control Module Installation (Side View)

Configuring the ComfortLinkt Controller

Configuration settings for the ComfortLink controller are
changed by using the Scrolling Marquee display. A password

may be required to edit the configurations, depending on the

previous settings configured in the unit. Default password is
“1111.” Use the arrow keys to scroll the red LED on the display

to the “Configuration” position and press

ENTER

. Scroll

through the menu until UNIT is found and press

ENTER

. After

reaching the UNIT sub-menu, scroll to FS.SW (Fire Shutdown
Input) and press

ENTER

twice, change the value to 1 (Normal

Open) with the arrow keys, press

ENTER

again. Press

ESCAPE

three times to return to the top level of the menu.

Additional information about changing configurations can be

found in the Control and Troubleshooting Guide for 48/50HG
and 48/50PG units.

OPERATION

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the

unit.
The smoke detector must be tested and maintained regularly

following NFPA 72 requirements. The smoke detector

should be cleaned at least once a year.

CAUTION

!

CR

S

M

K