Carrier 48SX024-060 User Manual

Page 19

Advertising
background image

Table 4A — Electrical Data — Unit 48SS

UNIT

SIZE

48SS

V-PH-Hz

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR-FAN

MOTOR

INDOOR-FAN

MOTOR

POWER SUPPLY

AWG 60 C

MIN WIRE

SIZE

MAX WIRE

LENGTH (ft)

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

018

208/230-1-60

187

253

8.3

45.0

0.7

1.8

12.9

15

14

75

024

208/230-1-60

187

253

12.4

61.0

0.7

2.0

18.2

30

12

80

030

208/230-1-60

187

253

14.4

82.0

1.4

2.3

21.4

30

10

100

208/230-3-60

187

253

9.4

66.0

1.4

2.0

15.1

25

12

80

036

208/230-1-60

187

253

18.0

96.0

1.4

2.8

26.7

40

10

90

208/230-3-60

187

253

11.7

75.0

1.4

2.8

18.8

30

12

65

460-3-60

414

506

5.6

40.0

0.8

1.4

9.2

10

14

100

042

208/230-1-60

187

253

20.4

104.0

1.4

4.0

30.9

50

8

100

208/230-3-60

187

253

14.0

91.0

1.4

4.0

22.9

35

10

85

460-3-60

414

506

6.4

42.0

0.8

2.0

10.8

15

14

100

048

208/230-1-60†

187

253

21.8

124.0

2.1

5.0

40.1

60

8

100

208/230-1-60**

187

253

26.4

129.0

2.1

5.0

40.1

60

6

100

208/230-3-60†

187

253

12.8

93.0

2.1

5.0

25.9

40

10

75

208/230-3-60**

187

253

15.0

99.0

2.1

5.0

25.9

40

10

75

460-3-60†

414

506

6.4

46.5

1.1

2.3

13.7

20

14

100

460-3-60**

414

506

8.2

50.0

1.1

2.3

13.7

20

14

100

060

208/230-1-60

187

253

32.1

169.0

2.1

6.8

49.0

60

6

100

208/230-3-60

187

253

19.3

123.0

2.1

6.8

33.0

50

8

90

460-3-60

414

506

10.0

62.0

1.1

3.2

16.8

25

12

100

LEGEND

AWG

American Wire Gage

FLA

Full Load Amps

HACR — Heating, Air Conditioning and

Refrigeration

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
RLA

Rated Load Amps

*Fuse or HACR Breaker.

† Carrier Scroll Compressor.
**Copeland Scroll Compressor.

NOTES:
1. In compliance with NEC (National Electrical Code) requirements

for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. The CGA (Canadian Gas As-
sociation) units may be fuse or circuit breaker.

2. Minimum wire size is based on 60 C copper wire. If other than

60 C wire is used, or if length exceeds wire length in table, de-
termine size from NEC.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.

% Voltage imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452

ϩ

464

ϩ

455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

19