CellarPro 4000SWC SPLIT SYSTEM WATER COOLED, 7649 User Manual

Page 10

Advertising
background image

10

V10.14

III.

Installation Instructions

Installation Instructions

Split System piping and wiring must be installed by a qualified Refrigeration
Technician in accordance with local and national code requirements.

Condensing Unit Installation


 Condensing units must be installed remotely from the cellar in an area protected

from direct exposure to moisture, sunlight, and temperatures below 40°F.

 The area must have suitable ventilation to maintain an ambient temperature of

110°F or less.

 If the area does not have adequate ventilation, a vent fan should be added to

supply fresh air to the space.


Evaporator Unit Installation

As warm air rises to the top of the cellar, the cooling unit pulls the warm air through
the evaporator coil and removes the heat from the warm air. Once cooled, the cold
air is discharged from the front of the cooling unit and circulates through the cellar.
Therefore, we recommend mounting the evaporator as close to the ceiling as
possible inside the cellar.