40

V10.14

Issues


Possible Causes


Possible Solutions

(Cont.) Iced Coil

Low refrigerant
charge

System charged incorrectly. Review process and
correct.

Leak in system. Find and repair leak, recharge
system.

Mal-functioning
thermostatic
expansion valve.

Incorrect superheat setting: determine superheat
and adjust. If expansion valve is faulty, replace.

Expansion valve bulb not located correctly -
review installation instructions and correct.

Liquid flashing at the expansion valve inlet. See
"High liquid line pressure drop" section.

Condensing unit
never shuts off

System is wired incorrectly. Locate correct wiring
diagram for “Electronic” or “Valve” controlled
system, trace wiring and correct.

If a “Valve” control system, the low pressure
switch may have failed closed. Check switch and
replace if necessary.

No airflow

See "Evaporator fan not blowing" section

Insufficient liquid sub-
cooling

Low refrigerant
charge

System charged incorrectly. Review process and
correct.

Leak in system. Find and repair leak, recharge
system.

High liquid line
pressure drop

Check for plugged filter drier and replace if
necessary.

Inspect pipe routing for proper piping practices
and correct.

Liquid line picking up too much ambient heat -
may need to insulate.