CellarPro MINI-SPLIT 3000S REFRIGERATION SYSTEM, 1713 User Manual

Page 25

Advertising
background image

25

V10.14

Line Sizing Chart
Refer to the Line Sizing Chart below for selecting the appropriate tubing size for
the length of the piping run. Note that the recommended line size may not match
the connection ports on the Condensing unit and the Evaporator. Refrigeration
grade fittings must be supplied by the installing technician to make the necessary
transitions. Transitions should be made as close to the unit as possible.
Suction line routing must be designed to ensure oil return to the Condensing unit.

Split System Line Sizing Chart

Model

Liquid Line

Size ("ODS)

Up to 100

feet

Minimum

Suction Line

Insulation

Thickness

(in)

Up to 25 feet

Over 25 feet

up to 50 feet

Over 50 feet

up to 100 feet

3000S/Sh

1/4

1/2

1/2

1/2

1/2

4000S/Sh

3/8

1/2

1/2

1/2

1/2

6000S

3/8

1/2

1/2

5/8

5/8

8000S

3/8

5/8

5/8

5/8

7/8

Notes:

1) Line lengths are expressed in equivalent feet = actual run length + fitting allowances.

3) Use only dehydrated refrigeration service tubing and refrigeration grade fittings.

4) Install refrigeration piping in accordance with local codes and ASHRAE guidelines.

Suction Line Size by Length ("ODS)

2) Chart includes allowances for Fittings, Filter Drier, and Sight Glass.

Vertical Piping Guidelines
Piping runs should be kept as short and compact as possible. Low-lying areas (oil
“traps”) where oil can accumulate should be avoided. Refer to the following
guidelines with regards to the vertical placement of the evaporator and condensing
units:

Advertising