7. Warm the bottom shell of the compressor above the ambient temperature for

30 minutes to drive excess refrigerant out of the compressor oil. Connect

power to the Evaporator and Condensing unit, and activate the system.

Check that the sight glass is clear when the compressor is running. The

condensing temperature must be above 105°F (135.0 PSIG) when inspecting

for a clear sight glass. In a low ambient environment, it may be necessary to

block off the condenser air intake to force the condensing temperature higher.

If the sight glass is not clear, slowly add vapor refrigerant though the suction

service valve.

8. With a clear sight glass, adjust the superheat on the thermostatic expansion

valve to 10°F +/- 2°F, as measured at the suction access valve located in the
Evaporator.

9. Once the superheat is adjusted, ensure the condenser face airflow is

unrestricted and allow the system to balance for 30 minutes.

10. Check the suction superheat at the compressor using the access port on the

suction service valve. A minimum superheat of 20°F is required at this
location. If it is below 20°F, recheck the thermostatic expansion valve
superheat and increase as necessary to ensure a 20°F superheat at the
compressor.

11. Adjust the fan cycling control (located on the Condensing unit) so that the

condenser fan cuts-out at approximately 90°F (104.5 PSIG), and cuts-in at
120°F (171.0 PSIG). Verify pressures with valve manifold gauges at startup.