V . T r o u b l e s h o o t i n g

Improper installation, inadequate insulation, or a cellar that is too large will
cause the cooling unit to run continuously and be difficult to troubleshoot.

The cooling unit is designed to turn on when the air temperature in the cellar rises
ABOVE the Minimum Set Point + Temperature Differential, and turn off when the air
temperature falls below the Minimum Set Point. For example, if the Minimum Set
Point is 58°F and the Temperature Differential is 4°F, the cooling unit will turn above
62°F and turn off below 58° F. In this example, the average temperature inside the
cellar will be 60°F.

Cooling Unit Runs Constantly

When bottles are first loaded in the cellar, the cooling unit will run continuously (even
up to a week) until the temperature inside the cellar falls below the Set Point.

Hot weather conditions, insufficient ventilation and/or dirty condenser filters may
cause the cooling unit to run continuously. To reduce cycle times,

1. Remove any obstructions to air flow to or from the unit
2. Check to make sure the condenser filter is clean

3. Increase the supply of cool air to the space outside the condenser coils, using a

fan, ducting or an exhaust system to remove heat from the space.

4. Raise the Minimum Set Point on the cooling unit

Cooling Unit Is Dripping

The cooling unit is designed to remove excess moisture from inside the cellar, which
collects in the drip pan of the cooling unit and is evaporated by the condensate
heater. Excess moisture can occur when the cooling unit runs constantly, when the
Minimum Set Point is too low and/or when the cellar doesn’t have a good seal from the
outside environment. To eliminate overflow, do the following:


1. Ensure the condensate overflow drain line is not blocked, that the drain line is

trapped and the trap is filled with water.

2. Check that the cellar has airtight seals, including the door(s), light fixtures, and all

walls, ceiling and floor.

3. Raise the Minimum Set Point of the cooling unit.

The Cooling Unit Won’t Turn On

The cooling system is programmed with a 3-Minute Delay at Startup to protect its
internal components.