Sh-35n instructionsoutside.pdf, Sh-35n, And sh-36n – Just Better SH-36N Obtaining Target Superheat Value User Manual

Page 2: Refrigeration applications, A/c & refrigeration applications, R404a

Advertising
background image

Not intended for use on hazardous or corrosive fluids

GAUGE SPECIFICATIONS:
Pressure display range:

29 InHg to 600 psig (-98kPa to 4134 kPa)
(+/- 1 PSI to 200 psi, 0.5% to 600 psi)

Temperature display range:

-40°F to 200°F (-40°C to 93°C)

Operating temperature:

-10°F to 120°F (-12°C to 49°C)
(+/- 1°F * 32°F/120°F, +/- 1.5°F * -10°F/32°F)

Maximum overpressure:

800 psig (5512 kPa)

Battery life and type:

100 hours/ 9vAlkaline battery

Auto-shutoff time:

60 minutes (extended 60 minutes by upper button action)

Refrigerant data source:

NIST REFRPRO software and manufacturers data

Uses one 9v Alkaline battery

(not included)

EXTENDING

AUTO-SHUTOFF TIME

Extend time by 60 minutes by

pressing upper button.
Push lower button 2 times to

select 1 hour or 24 hours.

SUPERHEAT

REFRIGERANT KE Y

(R410A Included)

TEMPERA TURE

SENSO R

2

1

R404A

HP62

PSI/F

MANUFACTURER’S DESIGNATION

“R” NUMBER

UNITS (F or C)

Only a properly charged unit will provide the owner

with the design SEER for maximum energy efficiency.

SUPERHEAT, TEMPERATURE,

SUBCOOLING AND PRESSURE

PUSH once to toggle between displays
PUSH 2 times to recall High, Low & Average

Hold down to clear memory.

ON/OFF

PUSH once to “Turn On”

Display shows LAST refrigerant used.

HOLD down to "Turn Off"

PUSH 2 times to select 1 hour or 24 hour auto-off mode

REFRIGERANT SELECTION

PRESS once at any time to display current refrigerant.

Continue pressing to scroll the refrigerant list.

(See list of refrigerants on page 4.)

Wait 1.5 seconds, then continue pressing to reverse

scroll direction.

APPLICATION TIPS:
Allow the manifold to Zero at Turn-On:

The manifold displays will zero (CAL) each time the

manifold is turned on without pressure . Zeroing the gauge

compensates the Pressure display for changes in (1) Altitude

and (2) Barometric pressure.

Pressure Calibration

Don’t be alarmed if your manifold gauge does not agree

with your mechanical gauges. The digital manifold is

calibrated with a very accurate pressure and is not affected

by vibration, motion or position.

Extending On-Time

The digital manifold will turn off automatically after 60

minutes to save battery life.

If any button is touched the digital manifold will stay on for

another 60 minutes.

Over/Under-Range Indicator

Pressures or temperatures below or above the rated

ranges will cause a “1” to be displayed.

Low Battery Indicator

Low batteries will be indicated by a blinking display.

Batteries For Low Temperature Applications

Using the gauge in a low temperature conditions will

shorten battery life. Change to

the 9 volt Lithium battery (Radio Shack 23-665) to solve

this problem.

REFRIGERANT KEY PLUG-IN

See page 4 for other

refrigerant keys available.

Metric and English keys are

not interchangeable.

SH-35N

(°F)

and SH-36N

(°C)

SUPERHEAT and SUBCOOLING GAUGE

OPERATING INSTRUCTIONS

REFRIGERATION APPLICATIONS

SETTING FOR THERMOSTAT

CONTROLLED CASES AND

COOLERS

Without plug-ins, turn on the gauge

and zero the display by holding

the lower button. Plug in the

Temperature Sensor only and toggle

to “Temperature.”

SETTING FOR THERMOSTAT

CONTROLLED CASES AND

COOLERS

Without plug-ins, turn on the gauge

and zero the display by holding the

lower button. Attempts to zero the

gauge with pressure applied will

result in (Err) display.

A/C & REFRIGERATION APPLICATIONS

Contact your TXV manufacturer for the exact superheat adjust rate.

0

5

10

15

20

25

20

18

16

14

12

10

8

6

4

Superheat

ϒF

Time in Minutes

Expansion Valve Superheat

SH-35N Average Superheat

Hussmann RHF A 4 Door FF Case

1 Ton Lo w Temp. TXV

-2 F Case Temperature

40% Heater Load

SET SUPERHEAT FOR

“HUNTING” TXV VALUES

In refrigeration and air

conditioning systems, the

expansion valve often

operates to produce an

evaporator superheat

which constantly swings up

and down in value, called

“hunting.” The SH-35N

provides the “Average”

superheat value for TXV

valve adjustment.

CHECKING TXV SETTING

The objectives of the TXV superheat setting is to prevent

liquid refrigerant floodback to the compresor and to

optimize system operation by the use of a selected setting.

The two temperature method of measuring superheat

is not recommended because it can produce a wrong

superheat measurement, due to the effect of temperature

glide of the blended refrigerants and variations in

evaporator pressure drop.

NEW RESIDENTIAL A/C SYSTEMS

For new installations of residential A/C systems, the pre-

charge will not provide an accurate amount of refrigerant

charge because of the variation in the length of liquid and

suction line connecting to the “A” coil.

RETROFITTING SYSTEMS

Retrofitting systems to a new refrigerant can change the

TXV superheat setting. The superheat setting should

be checked before and after retrofitting to be sure the

superheat is right for the equipment.

REPLACEMENT ITEMS

PART NO. DESCRIPTION

A34000 1/4" QC x 1/4" Access Branch Tee
SH-54

6' Temperature Sensor

SH-55

Plastic Carrying Case

SH-56

Socks (5)

ACCESSORIES

SH-51

28' Temperature Sensor Extension

KEY REFRIGERANT LIST “A”

R11

R12

R13

R22

R23

R134A

R290

R401A

R401B

R402A

R402B

R403B

R404A

R406A

R407A

R408A

R409A

R410A

R411C

R413A

R414B

R416A

R417A

R422A

R500

R502

R507

R508B

RB276

SUPERHEAT

JB INDUSTRIES

630.851.9444

Printed in USA

Part No. 10737-308

© 2006 J/B Industries Inc.

Technical service: 800-323-0811

E-Mail:[email protected]

Web Site:www.jbind.com

Fahrenheit and Celsius Keys are not interchangeable

SUPERHEAT

TEMPERA TURE

SENSOR

TEMP

PSI

R407B

R407C

R422B

Advertising
This manual is related to the following products: