Diff, Stpt – KMC Controls BAC-8007 Installation Guide User Manual

Page 30

Advertising
background image

Procedure

Detailed steps

STE display

10

Set the minimum
temperature differential
setpoint.

The minimum allowable temperature value
between the cooling and heating setpoints.

1.

Press the

or

buttons to set the

differential setpoint. The setpoint will change
in 1° increments.

2.

Press the

Set

Point

button to save the setpoint and

advance to the next function.

O5

DIFF

11

Set the standby
differential setpoint.

The standby setpoint is calculated by adding or
subtracting the offset value to or from the value
of the occupied setpoint.

1.

Press the

or

buttons to set the standby

differential setpoint. The setpoint will change
in 1° increments.

2.

Press the

Set

Point

button to save the setpoint and

advance to the next function.

OS

12

Select a new
configuration function or
exit.

1.

Press the

or

buttons to select one of the

following:

BOX

,

FLOW

,

ADVC

, or

RSTR

options

BACK

to choose another configuration

function.

EXIT

to return to the temperature display.

2.

Press the

Set

Point

button to select the next function.

STPT

Procedure to set the temperature setpoints (continued)

Section 4: Configuring the controllers

SimplyVAV

30

Revision E