Maintenance

Remove dust as necessary from the holes in the

cover. Clean the window with a soft, damp cloth and

mild soap if needed.

© 2012 KMC Controls, Inc.

877-019-01C

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Important Notices

The material in this document is for information

purposes only. The contents and the product it

describes are subject to change without notice.

KMC Controls, Inc. makes no representations or

warranties with respect to this document. In no event

shall KMC Controls, Inc. be liable for any damages,

direct or incidental, arising out of or related to the

use of this document.

For specifications, accessories list, and other informa-

tion, see the

CTE-5100 Series Data Sheet

.

Adjustments and Calibration

Thermal calibration is not required. Minimum and

maximum control points can be calibrated before or

after the thermostat has been installed.
1. Turn setscrews CW and remove cover.
2. Verify 16 VDC between the “+” and “–” terminals.
3. Remove setpoint slider stops (HFO-0027) if

necessary.

4. Measure “Tx” to “–” for output voltage. (See the

table on page 2 and the graphs on pages 3 and 4

to determine the correct T terminal.)

5. Maximum limits MUST be greater than

minimum limits. If in doubt, turn maximum limit

fully clockwise (increase) before proceeding.

NOTE: Dials rotate approximately 200° (8:00–4:00).

DO NOT force dial beyond stop.

6. Connect a voltmeter to the meter taps (using an

HSO-5001):
a. The two holes on the right are for the

minimum and maximum.

b. Measure actual flow in left holes. The

thermostat must be wired to a controller for

this option.

7. Always adjust the minimum first. Adjust setpoint

to request minimum flow using the minimum

dial:
• DA Cooling; Set point > Room Temp.
• RA heating; Set point < Room Temp.

NOTE : Limits may be set at the CSP series

controller or the thermostat. If setting min./

max. limits at the thermostat, the CSP’s

Min. dial must be turned fully CCW to “0”

AND the Max. dial must be turned fully

CW to “100.” This ensures that the CSP will

not affect the limits.

8. Adjust the setpoint to request maximum flow

using the Max. dial:
• RA Heating; Set point > Room Temp.
• DA Cooling; Set point < Room Temp.

9. Reinstall the cover and turn setscrews CCW until

the cover is secure.

More Information

For more wiring and calibration details as well as

sample applications, see the

CSP-5001/5002 Applica-

tions Guide.