TPE-1464 Series Gauge Pressure Transducers

2

Installation Guide

Wiring

This device is a 3-wire sourcing type transmitter.

Use 22 AWG shielded wiring for all connections.

Do not locate device wires in the same conduit as

wiring supplying inductive loads (such as motors).

Disconnect the power supply before making any

connections to prevent electrical shock or equipment

damage. Make all connections in accordance with

national and local electrical codes.
1. Connect the positive DC voltage or the hot side of

the AC voltage to the terminal marked PWR.

2. Connect the power supply common to the

terminal marked COM. The unit is reverse-

voltage protected and will not operate if

connected backwards.

The analog output signal is available on the OUT

terminal. This signal is jumper selectable for either

voltage or 4 to 20 mA output. In voltage mode, either

0 to 5 or 0 to 10 VDC can also be selected.

CAUTION

Do not connect power to the OUT terminal
because the device will be damaged.

The remote zero feature may be used by wiring a

dry-contact (relay only) digital output to the ZERO

terminals. Do not apply voltage to the ZERO termi-

nals.
NOTE: This is an active device. Turn Off the

relevant input pull-up resistor selector

switches on KMDigital and BACnet

controllers.