Menu configuration – KMC Controls SAE-1152(OLD Style Board w/ LEDs) User Manual
Page 5

Menu Configuration
Menu is controlled by using the four buttons on the circuit board (MENU, SAVE, UP and DOWN). Press
<MENU> to step through the selections. Use the <UP> and <DOWN> keys to make changes. No values are
saved or changed until you press the <SAVE> key. The <SAVE> key saves the current setting to memory,
exits the configuration menu, and returns to normal operation.
Press <MENU>
1. RESTORE DEFAULTS: All 5 LEDs flash to
indicate this mode. Press the <SAVE> key to
restore all factory defaults to their original
settings.
Press <MENU>
2. BUZZER TRIP=150:
D9 and D10 flash three times to indicate this
mode. The trip level is shown on the LEDs as a
5 bit binarynumber with D9 being the Least
Significant Bit.
Example:
100 ppm = 00000
110 ppm = 00001
400 ppm = 11110.
The factory default for the buzzer trip level is
150 ppm.
Press <MENU>
3. BUZZER DEL=5MIN:
D9 and D11 flash three times to indicate this
mode.
No LEDs lit = 0 minutes
D9 lit = 1 minute
D10 lit = 2 minutes, etc.
Press <MENU>
4. RELAY 1 TRIP=50
D9 and D12 flash three times to indicate this
mode. The trip level is shown on the LEDs as a
5 bit binarynumber with D9 being the Least
Significant Bit.
Example:
40 ppm = 00000
50 ppm = 00001
60 ppm = 00010
350ppm = 11111.
The factory default for relay 1 trip level is 50
ppm.
Press <MENU>
5. RELAY 1 HYST=10
D9 and D13 flash three times to indicate this
mode.
D9 = 10 ppm
D10 = 15 ppm, etc.
The factory default for relay 1 hysteresis is 10
ppm.
Press <MENU>
6. RELAY 1 DEL=2MIN
D10 and D11 flash three times to indicate this
mode.
No LEDs lit = 0 minutes
D9 lit = 1 minute
D10 lit = 2 minutes, etc.
The factory default is 2 minutes.
Press <MENU>
7. RELAY 2 TRIP=150
D10 and D12 flash three times to indicate this
mode. The trip level is shown on the LEDs as a 5
bit binary number with 9 being the Least
Significant Bit.
Example: 100 ppm = 00000
110 ppm = 00001
120 ppm = 00010
400 ppm = 11110
The factory default for relay 2 trip level is 150
ppm.
Press <MENU>
8. RELAY 2 HYST=25
D10 and D13 flash three times to indicate this
mode.
D9 = 10 ppm
D10 = 15 ppm, etc.
The factory default for relay 2 hysteresis is 25
ppm.