Menu Configuration

Menu is controlled by using the four buttons on the circuit board (MENU, SAVE, UP and DOWN). Press
<MENU> to step through the selections. Use the <UP> and <DOWN> keys to make changes. No values are
saved or changed until you press the <SAVE> key. The <SAVE> key saves the current setting to memory,
exits the configuration menu, and returns to normal operation.

Press <MENU>

1. RESTORE DEFAULTS: All 5 LEDs flash to

indicate this mode. Press the <SAVE> key to
restore all factory defaults to their original
settings.

Press <MENU>

2. BUZZER TRIP=150:

D9 and D10 flash three times to indicate this
mode. The trip level is shown on the LEDs as a
5 bit binarynumber with D9 being the Least
Significant Bit.

Example:

100 ppm = 00000
110 ppm = 00001
400 ppm = 11110.

The factory default for the buzzer trip level is
150 ppm.

Press <MENU>

3. BUZZER DEL=5MIN:

D9 and D11 flash three times to indicate this
mode.

No LEDs lit = 0 minutes
D9 lit = 1 minute
D10 lit = 2 minutes, etc.

Press <MENU>

4. RELAY 1 TRIP=50

D9 and D12 flash three times to indicate this
mode. The trip level is shown on the LEDs as a
5 bit binarynumber with D9 being the Least
Significant Bit.

Example:

40 ppm = 00000
50 ppm = 00001
60 ppm = 00010
350ppm = 11111.

The factory default for relay 1 trip level is 50
ppm.

Press <MENU>

5. RELAY 1 HYST=10

D9 and D13 flash three times to indicate this
mode.

D9 = 10 ppm
D10 = 15 ppm, etc.

The factory default for relay 1 hysteresis is 10
ppm.

Press <MENU>

6. RELAY 1 DEL=2MIN

D10 and D11 flash three times to indicate this
mode.

No LEDs lit = 0 minutes
D9 lit = 1 minute
D10 lit = 2 minutes, etc.

The factory default is 2 minutes.

Press <MENU>

7. RELAY 2 TRIP=150

D10 and D12 flash three times to indicate this
mode. The trip level is shown on the LEDs as a 5
bit binary number with 9 being the Least
Significant Bit.
Example: 100 ppm = 00000

110 ppm = 00001
120 ppm = 00010
400 ppm = 11110

The factory default for relay 2 trip level is 150
ppm.

Press <MENU>

8. RELAY 2 HYST=25

D10 and D13 flash three times to indicate this
mode.

D9 = 10 ppm
D10 = 15 ppm, etc.

The factory default for relay 2 hysteresis is 25
ppm.