SSS-1000 Series

2

Installation Guide

© 2014 KMC Controls, Inc.

655-019-01L

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Select Specifications

Material

Light gray (SSS-100x) or al-

mond (SSS-101x) ABS/polycar-

bonate (UL94-5V)

Connection

1/4" nipple (SSS-100x) for 3/8"

OD polyethylene tubing or

3/16" nipple

(

SSS-101x) for

1/4" OD tubing

K Factors

See the data sheet for addi-

tional information!

Maintenance

Sensing orifices must be kept free of dust ac-

cumulation or debris. The sensors are designed for

dependable, long-term reliability and performance.

Important Notices

The KMC logo and KMC Controls are registered

trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may

be reproduced, transmitted, transcribed, stored in a

retrieval system, or translated into any language in

any form by any means without the written permis-

sion of KMC Controls, Inc.
The material in this document is for information

purposes only. The contents and the product it

describes are subject to change without notice.

KMC Controls, Inc. makes no representations or

warranties with respect to this document. In no event

shall KMC Controls, Inc. be liable for any damages,

direct or incidental, arising out of or related to the

use of this document.

More Information

For additional K factor

and other information,

see the

SSS-1000 Series

Data Sheet

on the KMC

web site (

www.kmccon-

trols.com

).

“Cubic Feet Per Minute (CFM)” K Factors

Round

Duct Size

(Diameter)

K

CFM

Factor

SSS-10x2 SSS-10x3 SSS-10x4 SSS-10x5

4

301

NA

NA

NA

5

470

NA

NA

NA

6

677

648

NA

NA

7

922

882

NA

NA

8

1204

1152

1117

NA

9

1524

1458

1414

NA

10

1882

1800

1745

1745

12

2710

2592

2513

2513

14

3688

3528

3421

3421

16

4817

4608

4468

4468

18

6097

5832

5655

5655

22

9107

8711

8447

8447

24

10838

10367

10053

10053

“Feet Per Minute” K Factors

Sensor Model

K

FPM

SSS-10x2

3450

SSS-10x3

3300

SSS-10x4

3200

SSS-10x5

3200

NOTE: For the appropriate sensor “K” factor:

• For digital VAV controllers needing K

CFM

for setup,

see the “CFM” chart below and the data sheet for

additional information. For rectangular ducts,

K

CFM

= K

FPM

x (W" x H"/144)

2

(with duct cross-

section measurements in inches).

• For CSC-2000 series, CSC-3000 series, and CSP-

4000 series controllers (needing K

FPM

for setup),

see the “Feet Per Minute” chart below and the

data sheet for additional information.

• For CSP-5000, KMD-7000, and BAC-7000 series

that operate differently—see their respective in-

stallation guides and application guides for more

information.