Select Specifications
Material
Light gray (SSS-100x) or al-
mond (SSS-101x) ABS/polycar-
bonate (UL94-5V)
Connection
1/4" nipple (SSS-100x) for 3/8"
OD polyethylene tubing or
3/16" nipple
(
SSS-101x) for
1/4" OD tubing
K Factors
See the data sheet for addi-
tional information!
Maintenance
Sensing orifices must be kept free of dust ac-
cumulation or debris. The sensors are designed for
dependable, long-term reliability and performance.
Important Notices
The KMC logo and KMC Controls are registered
trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may
be reproduced, transmitted, transcribed, stored in a
retrieval system, or translated into any language in
any form by any means without the written permis-
sion of KMC Controls, Inc.
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
More Information
For additional K factor
and other information,
web site
).
“Cubic Feet Per Minute (CFM)” K Factors
Round
Duct Size
(Diameter)
K
CFM
Factor
SSS-10x2 SSS-10x3 SSS-10x4 SSS-10x5
4
301
NA
NA
NA
5
470
NA
NA
NA
6
677
648
NA
NA
7
922
882
NA
NA
8
1204
1152
1117
NA
9
1524
1458
1414
NA
10
1882
1800
1745
1745
12
2710
2592
2513
2513
14
3688
3528
3421
3421
16
4817
4608
4468
4468
18
6097
5832
5655
5655
22
9107
8711
8447
8447
24
10838
10367
10053
10053
“Feet Per Minute” K Factors
Sensor Model
K
FPM
SSS-10x2
3450
SSS-10x3
3300
SSS-10x4
3200
SSS-10x5
3200
NOTE: For the appropriate sensor “K” factor:
• For digital VAV controllers needing K
CFM
for setup,
see the “CFM” chart below and the data sheet for
additional information. For rectangular ducts,
K
CFM
= K
FPM
x (W" x H"/144)
2
(with duct cross-
section measurements in inches).
• For CSC-2000 series, CSC-3000 series, and CSP-
4000 series controllers (needing K
FPM
for setup),
see the “Feet Per Minute” chart below and the
data sheet for additional information.
• For CSP-5000, KMD-7000, and BAC-7000 series
that operate differently—see their respective in-
stallation guides and application guides for more
information.