KMC Controls STE-6015 User Manual

Installation guide, Room temperature sensors, Mounting 1

Advertising
background image

STE-6010/6011/6013/6015 Room Temperature Sensors

1

Installation Guide

2.438

2.250

R 3.094

R .187

.643

.450

STE-6013

STE-6011

.475

max.

STE-6010/6015

Modular

RJ-45

Jack

Four-pin

EIA-485
PC Data

Port

Clamp

(Screw-type)

Terminals

Clamp

(Screw-type)

Terminals

.149

Installation Guide

Room Temperature Sensors

STE-6010/6011/6013/6015

Mounting 1

Location and Cover Removal 1

STE-6010/6013/6015 Only

1

STE-6011 Only

1

Controller Connection 2

STE-6010/6015 2

STE-6011 2

STE-6013 2

Maintenance 2
More Information 2

Mounting

mended, and the size of the holes will then need

adjusting.)

4. Connect the wiring (see the Wiring section).
5. Reinstall the cover.

STE-6011 Only

Handy Box Installation (Recommended)
1. Mount a universal backplate HMO-6036/6036W

to the handy box using the two screws provided.

2. Remove the cover from the black base (see the

Location and Cover Removal section).

3. Connect the wiring (see the Wiring section).
4. Attach the base to the backplate using two screws.
5. Check that leads to the thermistor are straight

and the thermistor is completely extended.

6. Reinstall the cover.
Hollow Wall Installation
1. Remove the cover from the black base (see the

Location and Cover Removal section).

2. Use the back panel as a template to drill two holes

for mounting screws (7/64 inches or 3 mm in di-

ameter and 1.4 inches, 1-13/32 inches, or 35.6 mm

apart) and to cut a center hole (7/8 inch or 20 mm)

for the terminal block or jack.

3. Connect the wiring (see the Wiring section).
4. Attach the black base to the wall using two #6

self-threading screws. (Plastic anchors are recom-

mended, and the size of the holes will then need

adjusting.)

5. Check that leads to the thermistor are straight

and the thermistor is completely extended.

6. Reinstall the cover.

All dimensions

are in inches

Location and Cover Removal

Install the sensor on an inside wall where it can sense

the average room temperature and be away from

direct sunlight, heat sources, windows, air vents,

and air circulation obstructions (curtains, furniture,

etc.). It can be mounted on a hollow wall or (with

an HMO-6036/6036W universal backplate) to a 2 x 4

inch electrical (handy) box.
The cover is held to the black base by three round

pegs that fit in the holes of the cover. The bottom peg

is on a tab and snaps into the center bottom hole.
1. With a small Phillips screwdriver or hex wrench,

press in and hold the plastic tab button that

snaps into the center hole on the bottom of the

cover. Do not use excessive force and deform or

break the tab.

2. Carefully pull the cover from the black base.

STE-6010/6013/6015 Only

Handy Box Installation (Recommended)
1. Mount an HMO-6036 or HMO-

6036W universal backplate to the

handy box using the two screws

provided.

2. Remove the cover from the black base (see the

Location and Cover Removal section).

3. With the plastic tab button on the bottom, attach

the base to the universal backplate using the two

screws provided.

4. Connect the wiring (see the Wiring section).
5. Reinstall the cover.
Hollow Wall Installation
1. Remove the cover from the black base (see the

Location and Cover Removal section).

2. Using the base as a template, drill two holes for

mounting screws (7/64 inches or 3 mm in diam-

eter and 1.4 inches, 1-13/32 inches, or 35.6 mm

apart) and cut a center hole (size needed is depen-

dent on model) for the terminal block or jack.

3. Attach the base to the wall using two #6 self-

threading screws. (Plastic anchors are recom-

Advertising