2
Installation Guide
STE-6016
STE-6012
Wiring
Connecting the STE-6016 to a KMC controller
requires a special cable with (on the sensor end) an
RJ-45 connector and (on the controller end) an RJ-11
connector with an additional three wires (as relevant
to the model) for controller inputs. Purchasing
preassembled cables from KMC is more cost-
effective and reliable than creating custom cables in
the field. Use one of the following cables:
• KMD-5693 = 25 feet
• KMD-5694 = 50 feet
• KMD-5695 = 75 feet
The three additional wire connections to the control-
ler are:
• Orange is the 0–5 VDC temperature (scaled
voltage from thermistor) signal to the controller’s
appropriate input
• Orange/white is the 0–5 VDC setpoint signal to
the controller’s appropriate input
• Green is the supply voltage of 7.5 VDC (unoccu-
pied/setback mode) or 12 VDC (occupied/normal
mode) from an output of the controller
NOTE: In the STE-6012/6016, pressing the
Down
button momentarily sends 0 VDC to the
controller (via C terminal or orange wire)
for a SENSORON signal; pressing the
Up button sends greater than 5 VDC for
a SENSOROFF signal. When in occupied/
normal mode, pressing the Down or Up
button raises or lowers the setpoint voltage.
When in unoccupied/setback mode,
pressing either button also selects override
mode.
KMD-5693 = 25 feet; KMD-5694 = 50 feet; KMD-5695 = 75 feet
1
8
Orange Wire = 0–5 VDC Temperature Signal to Controller
Orange/White Wire = 0–5 VDC Setpoint Signal to Controller
12 inches
5
2
RJ-11 and
Wire Leads
to Controller
RJ-45
to STE
Sensor
Green Wire = 7.5/12 VDC Supply Voltage from Controller
RJ-11 RJ-45 Color
(Lead) 8 Orange
7 N.C.
(Lead) 6 Green
3
5
Blue
4
4
Blue/White
5
3
Green/White
2 N.C.
(Lead) 1 Orange/White
(Cables crossed, 20 AWG)
Common (“Ground”)
0–5 VDC Temperature Signal and (during a Button Press)
SENSORON (0 VDC on ) or SENSOROFF (> 5 VDC on )
D
B
C
A
0–5 VDC Setpoint Signal
7.5 VDC (Unoccupied/Setback) or
12 VDC (Occupied/Normal) Supply (from Controller)
{
{
{
{
© 2013 KMC Controls, Inc.
866-019-05D
More Information
For general product infor-
mation, see the
on the KMC Controls
web site.
For mounting consider-
ations, network connection,
controller configuration,
programming, troubleshoot-
ing, and other information,
.
Maintenance
Careful installation will also ensure long-term
reliability and performance. Remove dust as neces-
sary from holes in top and bottom. Clean with a soft,
damp cloth and mild soap.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com; [email protected]
Connect wires as shown for the relevant model.
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
Up (Toward Ceiling at Installation)