Connections and wiring, Setup, Calibration – KMC Controls TSP-6051 User Manual
Page 2: Maintenance, Important notices

TSP-6001/6051
2
Installation Guide
Connections and Wiring
Wiring Detail
Setup
The TSP-6001/6051 is factory calibrated to function
with the SSS-1002 through SSS-1005 differential
pressure pickups. Use 24" of 1/4" OD x 0.040" wall
“FR” instrument and control tubing, HFO-0108 1/4"
x 3/8" barb union fitting, and 1" of 3/8" OD x 0.062
wall “FR” tubing for both connections.
1. Connect “H” port to the “total velocity” (high side)
of the velocity pickup.
2. Connect the “L” port to the “static” (low side) of the
velocity pick up.
Calibration
The TSP-6001/6051 will have a range of 0–3,000 fpm
with a 0–5 VDC velocity output signal when using
any SSS-1002 through SSS-1005 velocity pickup. Fine
tuning to a specific range is possible.
NOTE: To complete these adjustments, the wiring
access door must be opened
by pulling back
on the door’s tab and lifting upward.
To set a range:
1. Apply the desired velocity pressure and
maximum flow to the “H” and “L” ports.
2. Adjust the SPAN potentiometer until the 0–5
VDC Velocity Output signal indicates 5 VDC
(reading between terminals “VEL” and “–”).
Important Notices
The material in this document is for information pur-
poses only. The contents and the product it describes
are subject to change without notice. KMC Controls,
Inc. makes no representations or warranties with respect
to this document. In no event shall KMC Controls, Inc.
be liable for any damages, direct or incidental, arising
out of or related to the use of this document.
Maintenance
No routine maintenance is required. Each compo-
nent is designed for dependable, long-term reliabil-
ity, and performance. Careful installation will also
ensure long-term reliability and performance.
NOTE: See the data sheet for a complete listing of
accessories as well as specifications.
1. Temporarily remove the
TSP-6001/6051
’s wiring
access door by pulling back on the door’s tab and
lifting upward.
2. Access for wire or cable is via two 5/8" (16 mm)
diameter snap-in shutter bushings located on the
rear of the
TSP-6001/6051
’s cover. (Remove the
snap-in shutter bushing and replace with the HMO-
4518 or HMO-4520 if required.)
3. Use the following accessories (ordered separately)
for the following connections to cable and conduit:
a. HMO-4518 for 1/2" flexible conduit.
b. HMO-4520 compression connector for plenum
rated cable.
c. HMO-4526 for rigid 1/2" conduit.
4. Wire the
TSP-6001/6051
as follows:
a. Terminal “VEL” to Velocity Output (0–5 VDC).
b. Terminal “Motor” to motor drive.
<
2 VDC = CCW
> 2.5 VDC = CW
2.25 VDC = Idle
c. Terminal “–” to “VEL” and “Motor” signal
ground.
d. Terminal “–” to 24 VAC Neutral.
e. Terminal “~” to 24 VAC Phase.
5. Reinstall the wiring access door.
NOTE: See also the Sample Application section
on the next page.