TSP-6001/6051

2

Installation Guide

Connections and Wiring

Wiring Detail

Setup

The TSP-6001/6051 is factory calibrated to function

with the SSS-1002 through SSS-1005 differential

pressure pickups. Use 24" of 1/4" OD x 0.040" wall

“FR” instrument and control tubing, HFO-0108 1/4"

x 3/8" barb union fitting, and 1" of 3/8" OD x 0.062

wall “FR” tubing for both connections.

1. Connect “H” port to the “total velocity” (high side)

of the velocity pickup.

2. Connect the “L” port to the “static” (low side) of the

velocity pick up.

Calibration

The TSP-6001/6051 will have a range of 0–3,000 fpm

with a 0–5 VDC velocity output signal when using

any SSS-1002 through SSS-1005 velocity pickup. Fine

tuning to a specific range is possible.
NOTE: To complete these adjustments, the wiring

access door must be opened

by pulling back

on the door’s tab and lifting upward.

To set a range:
1. Apply the desired velocity pressure and

maximum flow to the “H” and “L” ports.

2. Adjust the SPAN potentiometer until the 0–5

VDC Velocity Output signal indicates 5 VDC

(reading between terminals “VEL” and “–”).

Important Notices

The material in this document is for information pur-

poses only. The contents and the product it describes

are subject to change without notice. KMC Controls,

Inc. makes no representations or warranties with respect

to this document. In no event shall KMC Controls, Inc.

be liable for any damages, direct or incidental, arising

out of or related to the use of this document.

Maintenance

No routine maintenance is required. Each compo-

nent is designed for dependable, long-term reliabil-

ity, and performance. Careful installation will also

ensure long-term reliability and performance.

NOTE: See the data sheet for a complete listing of

accessories as well as specifications.

1. Temporarily remove the

TSP-6001/6051

’s wiring

access door by pulling back on the door’s tab and

lifting upward.

2. Access for wire or cable is via two 5/8" (16 mm)

diameter snap-in shutter bushings located on the

rear of the

TSP-6001/6051

’s cover. (Remove the

snap-in shutter bushing and replace with the HMO-

4518 or HMO-4520 if required.)

3. Use the following accessories (ordered separately)

for the following connections to cable and conduit:

a. HMO-4518 for 1/2" flexible conduit.
b. HMO-4520 compression connector for plenum

rated cable.

c. HMO-4526 for rigid 1/2" conduit.

4. Wire the

TSP-6001/6051

as follows:

a. Terminal “VEL” to Velocity Output (0–5 VDC).
b. Terminal “Motor” to motor drive.
<

2 VDC = CCW

> 2.5 VDC = CW

2.25 VDC = Idle
c. Terminal “–” to “VEL” and “Motor” signal

ground.

d. Terminal “–” to 24 VAC Neutral.
e. Terminal “~” to 24 VAC Phase.

5. Reinstall the wiring access door.

NOTE: See also the Sample Application section

on the next page.