KMC Controls TSP-8001 User Manual

Installing a simplyvav secondary actuator 1

Advertising
background image

These are brief instructions for installing a SimplyVAV

secondary damper actuator for dual-duct

installations. To view a short video of this

procedure or to download a PDF of The

SimplyVAV Installation and Applications

Guide, browse to the simplyVAV web site.

3

Connect the airflow sensors

Connect the airflow sensor on the VAV box to the

airflow ports on the controller. Use 0.25 in. FR

tubing.

4

Connect to primary controller

Connect the actuator to the SimplyVAV primary

controller. Wiring diagrams are part of the

SimplyVAV Installation and Applications Guide

and submittal sheets that can be found on the

Resources page of the SimplyVAV web site.

Drive hub

and V-bolt

Airflow sensor ports

Gear clutch

button

Mounting tab and

bushing

Black power

terminals

Green terminals

for connections to

primary controller.

Installing a SimplyVAV secondary actuator

1

Align the damper and drive hub

Manually rotate the damper on the VAV box to the

fully open position.
Press the gear clutch button and rotate the drive

hub in the same direction that opened the damper.

Turn the hub until it reaches a stop.

2

Mount the actuator to the VAV box.

Place the actuator over the damper shaft.
Finger tighten the nuts on the V-bolt to position the

shaft in the drive hub.
Center the mounting bushing in the mounting tab

and fasten it with a #8 sheet metal screw.
Evenly tighten the V-bolt nuts on the drive hub to

30-35 in-lbs.

915-019-05A

© 2014 KMC Controls, Inc.

Advertising