Rice Lake SCT-10 User Manual
Page 53
Operation 49
Example 2
Command for multiple writing of registers (hexadecimal command 16, h10):
Assuming that we wish to write the two setpoint values on the instrument, at
2000 and 3000 respectively, the string must be sent:
h01 h10 h00 h10 h00 h04 h08 h00 h00 h07 hD0 h00 h00 h0B hB8
hB0 hA2
The instrument will respond with the string:
h01 h10 h00 h10 h00 h04 hC0 h0F
Query Field Name
Hex
Response Field Name
Hex
Instrument Address
h01
Instrument Address
h01
Function h10
Function
h10
Address of the first register H
h00
Address of the first register H
h00
Address of the first register L
h10
Address of the first register L
h10
Number of registers to send H h00
Number of registers H
h00
Number of registers to send L h04
Number of registers L
h04
Byte Count
h08
CRC16 H
hC0
Datum 1 H
h00 CRC16
L
h0F
Datum 1 L
h00
Datum 2 H
h07
Datum 2 L
hD0
Datum 3 H
h00
Datum 3 L
h00
Datum 4 H
h0B
Datum 4 L
hB8
CRC16 H
hB0
CRC16 L
hA2