Smart Power Systems LR Series User Manual

Page 29

Advertising
background image

Smart Power

®

Systems

A. C. MODULAR GENERATOR SYSTEM

Page 28 of 49

8.

If the system measures a hydraulic oil temperature that exceeds 175°F (79°C), the
system will begin displaying an alarm. If the system measures a hydraulic oil
temperature that exceeds 180°F (82°C), the generator will automatically shut down
in 30 minutes unless the shutdown is overridden. If the temperature of the hydraulic
oil is measured at or above 220°F, the system will immediately shut down whether
or not the high temperature oil warning is overridden. To override the shutdown,
perform the following steps:

Note: The system must measure a hydraulic oil temperature that exceeds 180°F for
this procedure to work.

Step a: Press Mode to
cause

rvn

and the

y

and

n labels to appear.

Step b: Press On/Off to
answer “yes” and make
the next screen appear.

Example of Command & Control Center in hot oil fault override

Figure 19


a. From the Normal mode display, press Mode, as if you wanted to display the oil

temperature. The screen shown in Figure 19 will be displayed instead, asking if
you want to “Run hot.” This screen will also be displayed if you attempt to start
the generator with the condition present.


b. Note the y and n labels below the Mode and On/Off switches. Press the On/Off

switch to answer “yes” and proceed to the next screen, or press Mode to answer
“no” and proceed to the oil temperature display.