Tjernlund 950-0484 Mac-3 (Discontinued - No longer available) Board Kit 8505009 Rev. 08/00 User Manual

Page 3

Advertising
background image

CAUTIONS

1. Failure to install, maintain and/or operate the MAC-3 in accordance with manufacturer’s instructions may result in conditions that

can produce bodily injury and property damage.

2. The safety interlock and system operation performance checks must be performed on each appliance interlocked with the

MAC-3 in accordance with the Power Venter, Draft Inducer, IN-FORCER or Damper installation instructions.

ELECTRICAL

All wiring from the MAC-3 to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermediate conduit,
rigid non-metallic conduit, electrical metallic tubing, Type MI Cable, Type MC Cable or be otherwise suitably protected from physical damage.

The disconnect means and circuit protection are to be provided by the installer of this device.

SEQUENCE OF OPERATION OF MAC-3 INTERLOCKED WITH 24 VAC & 115 VAC APPLIANCE CONTROL CIRCUITS
The circuit board of the MAC-3 is designed for a simple three wire interlock with up to three separate burners. Upon a call for heat the “hot”
leg of the burner circuit is intercepted and routed to the MAC-3 terminal strip. The MAC-3 is activated, the power venter, draft inducer,
IN-FORCER or damper starts. The proving switch makes and the intercepted “hot” leg is returned to the burner circuit, allowing the burner to
fire. Plug-in relays must be purchased separately depending on control system voltage of appliance.

Use Tjernlund part # 950-1040 relay For 24 VAC control systems
Use Tjernlund part # 950-0480 relay For 115 VAC control systems

1

ELECTRICAL SPECIFICATIONS TABLE

Optional Limit (Spill Switch)

Used in conjunction with Optional Alarm
Sequencer

115 VAC Proven “HOT” From Fan Prover

115 VAC Neutral To Inducer / Venter / IN-FORCER

115 VAC “HOT” To Inducer / Venter
/ IN-FORCER motor & Fan Prover

Auxiliary Operation Switch
(i.e. Manual or Gas Pressure)

115 VAC Input From Disconnect Switch

Aux. Motor in parallel with H & N used for
additional Power Venter, Inducer, IN-FORCER

Aux. Prover contacts in series with H & PH
contacts on output terminals

Appliance # 2
Interlock

Appliance # 1
Interlock

Appliance # 3
Interlock

MAC-3 CIRCUIT BOARD FEATURES

Aux. Limit switch in series with
optional limit on terminal strip

Optional Alarm Sequencer proves Fan
Prover Operation (not limit operation)