ELECTRICAL WIRING CONNECTIONS

The electrical contact ratings for the Oil Solenoid Valve and the Relay are as follows:

OIL SOLENOID VALVE: 0.115 Amps at 120 VAC

RELAY: 0.10 Amps at 120 VAC (Coil), 12 Amps (full load) at 124 VAC (Contacts), 60 Amps (locked rotor) at 125 VAC (Contacts)

Make sure all power is disconnected from the furnace/boiler before attempting to install the ND-1. Failure to do so can cause electrical shock
resulting in personal injury or death.

All wiring from the to the post purge kit must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermediate metal conduit,
rigid non-metallic conduit, electrical metallic tubing, Type MI Cable, Type MC Cable, or be otherwise suitably protected from physical damage.

HST-SERIES WIRED WITH HONEYWELL ST9103 CONTROL AND BURNER MOTOR POST PURGE KIT

SIDESHOT® WIRED WITH STANDARD HONEYWELL ST9103 CONTROL & BURNER MOTOR POST PURGE

SIDESHOT

TERMINAL

STRIP

THERMOSTAT

TERMINAL

STRIP

FURNACE

TERMINAL

STRIP