Tjernlund PS1505 Fan Prover  8504008 Rev 1 01/97 User Manual

Page 2

Advertising
background image

GAS WIRING TO ANY APPLIANCE EQUIPPED WITH 24V CONTROLS

NO POST-PURGE RELAY/TIMER ON DRAFT INDUCER

GAS WIRING TO ANY APPLIANCE EQUIPPED WITH 24V CONTROLS

POST-PURGE RELAY/TIMER ON DRAFT INDUCER

(DRAFT INDUCER MOTOR LESS THAN 4.4 AMPS)

MODELS I, IL, XL MUST USE 950-0483 ISOLATION RELAY

COMPONENTS NEEDED:

(1) DRAFT INDUCER
(1) PS1505 FAN PROVER
(1) 950-1067 RELAY/TIMER

MAXIMUM AMP LOAD
IS 4.4 AMPS

USE ISOLATION RELAY ON
RELAY/TIMER IF MOTOR IS OVER
4.4 AMPS. SEE ISOLATION RELAY
DIAGRAM TOP RIGHT.

DRAFT INDUCER CONNECTED TO OIL BURNER WITH R8184G CONTROLS

(DRAFT INDUCER MOTOR LESS THAN 4.4 AMPS) MODELS I, IL, XL MUST USE 950-0483 ISOLATION RELAY

COMPONENTS NEEDED:

(1) DRAFT INDUCER
(1) PS1505 FAN PROVER
(1) 950-1067 RELAY/TIMER

MAXIMUM AMP LOAD IS
4.4 AMPS. USE ISOLATION
RELAY ON RELAY/TIMER IF
MOTOR IS OVER 4.4 AMPS.
SEE ISOLATION RELAY
DIAGRAM TOP RIGHT.

COMPONENTS NEEDED:

(1) DRAFT INDUCER
(1) PS1505 FAN PROVER
(1) 24/115V RELAY

USE 950-1040 FOR MODELS DJ3 & D3
USE 950-1016 FOR MODELS I, IL, XL

COMPONENTS NEEDED:

(1) DRAFT INDUCER
(1) RELAY/TIMER 950-1067

MAXIMUM AMP LOAD IS 4.4 AMPS. USE ISOLATION
RELAY ON RELAY/TIMER IF MOTOR IS OVER 4.4
AMPS. SEE ISOLATION RELAY DIAGRAM TOP RIGHT.

(1) WHK-I KIT
(1) 950-0470 THERMOCOUPLE JUNCTION

ADAPTER (FOR RESIDENTIAL WATER HEATERS ONLY)

GAS WIRING TO ANY APPLIANCE WITH MILLIVOLT CONTROLS

REQUIRES POST-PURGE RELAY/TIMER ON DRAFT INDUCER

(DRAFT INDUCER MOTOR LESS THAN 4.4 AMPS)

MODELS I, IL, XL MUST USE 950-0483 ISOLATION RELAY

RELAY/TIMER ISOLATION RELAY WIRING

DRAFT INDUCER MOTORS

GREATER THAN 4.4 AMPS

INCLUDES MODELS I, IL, XL

IF DRAFT INDUCER MOTOR IS OVER 4.4
AMPS, WIRE 950-0483 ISOLATION RELAY
AS SHOWN IN THIS DIAGRAM.

Note: For further assistance call Tjernlund Products, Inc.

Technical Customer Service Department at 1-800-255-4208.